4.3 FACEPLATE INTERFACE
ENTER COMMAND
PASSWORD
Press USER 1
To Select Breaker
BKR1-(Name) SELECTED
USER 2=CLS/USER 3=OP
(1)
USER 2 OFF/ON
To Close BKR1-(Name)
(2)
USER 3 OFF/ON
To Open BKR1-(Name)
4
(3)
BKR2-(Name) SELECTED
USER 2=CLS/USER 3=OP
e) CONTROL OF ONE BREAKER
For this application the relay is connected and programmed for breaker 1 only. Operation for this application is identical to
that described above for two breakers.
a) NAVIGATION
Press the MENU key to select a header display page (top-level menu). The header title appears momentarily followed by a
header display page menu item. Each press of the MENU key advances through the following main heading pages:
Actual values
Settings
Commands
Targets
User displays (when enabled)
b) HIERARCHY
The setting and actual value messages are arranged hierarchically. The header display pages are indicated by double
scroll bar characters (), while sub-header pages are indicated by single scroll bar characters (). The header display
pages represent the highest level of the hierarchy and the sub-header display pages fall below this level. The MESSAGE
4-26
This message appears when the USER 1, USER 2, or USER 3 key is pressed and a
is required; i.e. if
COMMAND PASSWORD
mands have been issued within the last 30 minutes.
This message appears if the correct password is entered or if none is required. This mes-
sage displays for 30 seconds or until the USER 1 key is pressed again.
This message is displayed after the USER 1 key is pressed for the second time. Three
possible actions can be performed from this state within 30 seconds as per items (1), (2)
and (3) below:
If the USER 2 key is pressed, this message appears for 20 seconds. If the USER 2 key is
pressed again within that time, a signal is created that can be programmed to operate an
output relay to close breaker 1.
If the USER 3 key is pressed, this message appears for 20 seconds. If the USER 3 key is
pressed again within that time, a signal is created that can be programmed to operate an
output relay to open breaker 1.
If the USER 1 key is pressed at this step, this message appears showing that a different
breaker is selected. Three possible actions can be performed from this state as per (1),
(2) and (3). Repeatedly pressing the USER 1 key alternates between available breakers.
Pressing keys other than USER 1, 2, or 3 at any time aborts the breaker control function.
D60 Line Distance Protection System
4 HUMAN INTERFACES
is enabled and no com-
COMMAND PASSWORD

4.3.7 MENUS