Advertisement

Interrupts/diagnostic messages
5.4 Interrupts
5.4.2

Cause of the error triggering a diagnostic interrupt

Which errors can trigger a diagnostic interrupt?
The technology module can trigger the following diagnostic interrupts:
Table 5- 6
Possible diagnostic interrupts
Diagnostic interrupt
Error
Parameter assignment error
Module temporarily unavailable
Internal error
Watchdog tripped. Module is defective.
RS422/TTL error
Load voltage missing
Hardware interrupt lost
Short circuit or overload at external encoder supply
Error at the digital outputs
Supply voltage error
Error at SSI encoder
Illegal A/B signal ratio
Overheating
Not available in "Position input for Motion Control" and "Fast Mode"
1
66
1
Monitoring
Monitoring is always active. A diagnostic interrupt is trig-
gered each time an error is detected.
Monitoring is always active. A detected error only triggers a
diagnostic interrupt if "Enable diagnostic interrupt for wire
break" has been enabled in the device configuration.
Monitoring is always active. A detected error only triggers a
diagnostic interrupt if "Enable additional diagnostic inter-
rupts" has been enabled in the device configuration.
Technology module TM PosInput 1 (6ES7138-6BA00-0BA0)
Manual, 04/2016, A5E33015755-AC