Parameter data record
Bit →
Bit 7
Byte ↓
6...7
6
Reserved
2)
7
Reaction to signal N:
00
: No reaction to sig-
B
nal N
01
: Synchronization at
B
signal N
10 to 11
: Invalid
B
84
Bit 6
Bit 5
Counter inputs (parameters for incremental encoders and pulse encoders)
Signal evaluation:
00
: Single
B
01
: Double
B
10
: Quadruple
B
11
: Invalid
B
Invert direc-
Enable
tion
diagnostic
1)
interrupt on
wire break
Bit 4
Bit 3
Signal type:
0000
: Pulse (A)
B
0001
: Pulse (A) and direction (B)
B
0010
: Count up (A), count down (B)
B
0011
: Incremental encoder (A, B phase-shifted)
B
0100
: Incremental encoder (A, B, N)
B
0101
: Absolute encoder (SSI)
B
0110 to 1111
: Invalid
B
Filter frequency
0000
: 100 Hz
B
1)
0001
: 200 Hz
B
0011
: 1 kHz
B
0100
: 2 kHz
B
0101
: 5 kHz
B
0110
: 10 kHz
B
0111
: 20 kHz
B
1000
: 50 kHz
B
1001
: 100 kHz
B
1010
: 200 kHz
B
1011
: 500 kHz
B
1100
: 1 MHz
B
1101 to 1111
: Invalid
B
Technology module TM PosInput 1 (6ES7138-6BA00-0BA0)
Bit 2
Bit 1
:
4)
Manual, 04/2016, A5E33015755-AC
Bit 0