Interrupts/diagnostic messages
5.3 Diagnostic messages
5.3
Diagnostic messages
Diagnostic alarms
If a diagnostic alarm is pending, the DIAG LED flashes red.
The diagnostics are displayed as plain text in STEP 7 (TIA Portal) in the online and
diagnostics view. You can evaluate the error codes with the user program.
The following diagnostics can be signaled:
Table 5- 5
Diagnostic alarms, their meaning and remedies
Diagnostic alarm
Error
code
Error
9
H
Parameter as-
10
H
signment error
Load voltage miss-
11
H
ing
Hardware interrupt
16
H
lost
Module temporari-
1F
H
ly unavailable
Internal error
100
Watchdog tripped.
103
Module is defec-
tive.
62
Meaning
Internal module error occurred
•
Possible cause: Technology module de-
•
fective
The received parameter data record is
•
invalid
The configured BaseUnit is not the used
•
BaseUnit
No technology module L+ supply voltage
•
Possible cause: BaseUnit-Incorrect type
•
Technology module cannot send an inter-
•
rupt because a previous interrupt has not
been processed
Possible causes:
•
–
Parameter assignment error
–
Too many hardware interrupts in too
short a time
No normal operation of the technology
•
module possible
Possible cause: Technology module is
•
performing a firmware update
Technology module defective
H
Firmware error
H
Technology module defective
To correct or avoid errors
Replace technology module
Checking parameter data record
•
Checking BaseUnit
•
Check BaseUnit type
•
Check the wiring of the supply voltage
•
L+ on the BaseUnit
Change interrupt processing in the CPU
•
and re-assign technology module pa-
rameters correspondingly
Checking frequency of the interrupts
•
from the process
Wait until technology module is availa-
•
ble again
If firmware update aborts:
•
–
Check minimum firmware version
required
–
Check supply voltage
–
Repeat firmware update
Replace technology module
Run firmware update
Replace technology module
Technology module TM PosInput 1 (6ES7138-6BA00-0BA0)