Interrupts/diagnostic messages
5.2 Parameter validation error
Error codes
If you are using an incremental encoder or pulse encoder, WRREC can include the following
error codes after transfer of a parameter data record to the module:
Error code
Parameter
11
Operating mode
H
12
Response to a CPU Stop
H
13
Signal type
H
15
Filter frequency for counter inputs
H
16
Reaction to signal N
H
17
Setting function of the DI
H
18
Setting function of the DI (DI0)
•
H
Setting function of the DI (DI1)
•
19
Setting function of the DI (DIm)
•
H
Edge selection (DIm)
•
1A
Input delay for digital inputs
H
1B
Set output
H
1C
Count direction of the DQ function
H
1D
Reset when counting limit is violated
H
1E
Reaction to violation of a counting limit
H
20
Reaction to gate start
H
21
H 1
Counter low limit
•
Comparison value 0
•
Comparison value 1
•
22
H 1
Counter high limit
•
Comparison value 0
•
Comparison value 1
•
23
Counter low limit
•
H
Start value
•
24
Counter high limit
•
H
Start value
•
25
Update time
H
58
Validation criteria
Invalid value
Invalid value
Invalid value
Invalid value
Invalid value
Invalid value
The same function is configured for DI0 and DI1
Invalid value
•
"Gate start (edge-controlled)" configured as function for DIm
•
and "At rising and falling edge"
"Gate stop (edge-controlled)" configured as function for DIm
•
and "At rising and falling edge"
"Synchronization" configured as function for DIm and "At
•
rising and falling edge"
Invalid value
Invalid value
Invalid value
Invalid value
Invalid value
Invalid value
Counter low limit > comparison value 0/1
Counter high limit < comparison value 0/1
Start value < Counter low limit
Start value > Counter high limit
Higher than maximum value
Technology module TM PosInput 1 (6ES7138-6BA00-0BA0)
Manual, 04/2016, A5E33015755-AC