Advertisement

Interrupts/diagnostic messages
5.2 Parameter validation error

Error codes

If you are using an incremental encoder or pulse encoder, WRREC can include the following
error codes after transfer of a parameter data record to the module:
Error code
Parameter
11
Operating mode
H
12
Response to a CPU Stop
H
13
Signal type
H
15
Filter frequency for counter inputs
H
16
Reaction to signal N
H
17
Setting function of the DI
H
18
Setting function of the DI (DI0)
H
Setting function of the DI (DI1)
19
Setting function of the DI (DIm)
H
Edge selection (DIm)
1A
Input delay for digital inputs
H
1B
Set output
H
1C
Count direction of the DQ function
H
1D
Reset when counting limit is violated
H
1E
Reaction to violation of a counting limit
H
20
Reaction to gate start
H
21
H 1
Counter low limit
Comparison value 0
Comparison value 1
22
H 1
Counter high limit
Comparison value 0
Comparison value 1
23
Counter low limit
H
Start value
24
Counter high limit
H
Start value
25
Update time
H
58
Validation criteria
Invalid value
Invalid value
Invalid value
Invalid value
Invalid value
Invalid value
The same function is configured for DI0 and DI1
Invalid value
"Gate start (edge-controlled)" configured as function for DIm
and "At rising and falling edge"
"Gate stop (edge-controlled)" configured as function for DIm
and "At rising and falling edge"
"Synchronization" configured as function for DIm and "At
rising and falling edge"
Invalid value
Invalid value
Invalid value
Invalid value
Invalid value
Invalid value
Counter low limit > comparison value 0/1
Counter high limit < comparison value 0/1
Start value < Counter low limit
Start value > Counter high limit
Higher than maximum value
Technology module TM PosInput 1 (6ES7138-6BA00-0BA0)