Technology module tm posinput 1
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Configuring/address space
4.4 Parameters
Parameter
Behavior of DI
Select edge for DI
1
Input delay for digital inputs
Comparison value 0
1
Comparison value 1
1
Measured variable
Update time [μs] of the measuring
function
1
Time base for velocity measure-
ment
1
Increments per unit
1
Hysteresis
1
Steps per revolution:
3
46
Value range
Capture
Digital input without function
At rising edge
At falling edge
At rising and falling edge
1
None
0.05 ms
0.1 ms
0.4 ms
0.8 ms
1.6 ms
3.2 ms
12.8 ms
20 ms
-2147483648...2147483647
(Fast Mode: 0...33554431)
-2147483648...2147483647
(Fast Mode: 0...33554431)
Frequency
Period
Velocity
Complete SSI frame
0...25000000
1 ms
10 ms
100 ms
1 s
60 s/1 min
1...65535
0...255
1...65535
Default setting
DI0, DI1:Digital input with-
out function
At rising edge
0.1 ms
0
10
Frequency
10000 (corresponds to
10 ms)
60 s/1 min
1
0
1
Technology module TM PosInput 1 (6ES7138-6BA00-0BA0)
Manual, 04/2016, A5E33015755-AC
Re-
configuration
in RUN
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes