Siemens SIMATIC ET 200SP Manual page 55

Technology module tm posinput 1
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Meaning of the LED displays
The following tables explain the meaning of the status and error displays. Remedial
measures for diagnostic alarms can be found in the section Diagnostic messages (Page 62).
Table 5- 1
Status and error displays DIAG
LED DIAG
Backplane bus supply of the ET 200SP not OK
Off
Technology module not configured
Flashes
Technology module configured but no module
diagnostics
On
Technology module configured and module diag-
nostics (at least one error pending)
Flashes
Table 5- 2
PWR/24VDC status displays
LEDs
PWR
24VDC
Off
Off
On
On
On
Off
Technology module TM PosInput 1 (6ES7138-6BA00-0BA0)
Manual, 04/2016, A5E33015755-AC
Meaning
Meaning
No supply voltage
Supply voltage is present and OK
Short-circuit or overload at the encoder
supply or supply voltage too low
Interrupts/diagnostic messages
5.1 Status and error displays
To correct or avoid errors
Check the supply voltage or turn it on at the inter-
face module.
---
Evaluate the diagnostic alarms and eliminate the
error.
To correct or avoid errors
Check the supply voltage.
Check the BaseUnit type and the wiring of
the BaseUnit.
---
Check the encoder wiring.
Check the loads connected to the encod-
er supply.
Check the supply voltage.
55

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents