Diagnostic alarm
Error
code
Short circuit or
10E
overload at exter-
nal encoder supply
Error at the digital
10F
outputs
Supply voltage
110
error
Illegal A/B signal
500
ratio
RS422/TTL error
502
Technology module TM PosInput 1 (6ES7138-6BA00-0BA0)
Manual, 04/2016, A5E33015755-AC
Meaning
Error at encoder supply
•
H
Possible causes:
•
–
Short circuit
–
Overload
Error at the digital outputs
•
H
Possible causes:
•
–
Short circuit
–
Overload
Error at supply voltage L+
•
H
Possible causes:
•
–
Low voltage
–
Wiring of L+ supply voltage defective
Time profile of signals A and B of the
•
H
incremental encoder does not meet cer-
tain specifications
Possible causes:
•
–
Signal frequency too high
–
Encoder faulty
–
Process wiring faulty
Error at connection of the RS 422, TTL
•
H
encoder or SSI absolute encoder
Possible causes:
•
–
Wire break
–
No encoder connected
–
Cable too long
–
Short circuit
–
Overload
–
External voltage
–
Overheating
–
Parameter assignment error
Interrupts/diagnostic messages
5.3 Diagnostic messages
To correct or avoid errors
Check encoder wiring
•
Check consumers connected to encoder
•
supply
Check wiring at the digital outputs
•
Check consumers connected to the
•
digital outputs
Check the L+ supply voltage
•
Check the wiring of the supply voltage
•
L+ on the BaseUnit
Checking total consumption of the load
•
group
Check process wiring
•
Check encoder/sensor
•
Check parameter assignment
•
Check process wiring
•
Check encoder/sensor
•
Check parameter assignment
•
63