Diagnostic alarm
Error
code
Short circuit or
10E
overload at exter-
nal encoder supply
Error at the digital
10F
outputs
Supply voltage
110
error
Illegal A/B signal
500
ratio
RS422/TTL error
502
Technology module TM PosInput 1 (6ES7138-6BA00-0BA0)
Manual, 04/2016, A5E33015755-AC
Meaning
Error at encoder supply
H
Possible causes:
Short circuit
Overload
Error at the digital outputs
H
Possible causes:
Short circuit
Overload
Error at supply voltage L+
H
Possible causes:
Low voltage
Wiring of L+ supply voltage defective
Time profile of signals A and B of the
H
incremental encoder does not meet cer-
tain specifications
Possible causes:
Signal frequency too high
Encoder faulty
Process wiring faulty
Error at connection of the RS 422, TTL
H
encoder or SSI absolute encoder
Possible causes:
Wire break
No encoder connected
Cable too long
Short circuit
Overload
External voltage
Overheating
Parameter assignment error
Interrupts/diagnostic messages
5.3 Diagnostic messages
To correct or avoid errors
Check encoder wiring
Check consumers connected to encoder
supply
Check wiring at the digital outputs
Check consumers connected to the
digital outputs
Check the L+ supply voltage
Check the wiring of the supply voltage
L+ on the BaseUnit
Checking total consumption of the load
group
Check process wiring
Check encoder/sensor
Check parameter assignment
Check process wiring
Check encoder/sensor
Check parameter assignment