Chapter 5 Parameters
0: disabled
No additional summing operation to the sum of
main freq. and auxiliary freq. See Fig. 5-58.
1: regulate based on max. output freq. (F005)
Preset freq. f4=f3+F0.05×(F9.06-100%)
2: regulate based on current output freq. (F005)
Preset freq.f4=f3+f3× (F9.06-100%)=f3×F9.06
F9.07 STOP/RESET key's
function and keypad lock
This function defines the function of
STOP/RESET key and keypad lock selection.
Thou. Hun. Ten One
Fig. 5-63 Stop/Reset Key's Function and
Keypad Lockup
One's place: STOP/RESET key's function
It is to set the usage and function of
STOP/RESET key when you want to stop the
drive.
0: effective when keypad control is selected.
1: effective for keypad, terminal and serial port
control. Press this key and the drive will stop in
specified manner.
2: effective for keypad, terminal and serial port
control. In keypad control mode, press this key
Range: 000 ~ 402 【 000 】
STOP/RESET
0: Active in keypad control mode
1: Active in all control modes
2: Active in keypad control mode,
drive displays E015 if used in
other control modes
Reserved
Keypad lock-up
0: No lock up
1: Lock up
2: Lock all the keys except STOP
3: Lock up all the keys except
4: Lock up except RUN and STOP
Reserved
EV1000 Series General Purpose Variable Speed Drive User Manual
and the drive will stop in specified manner. But in
terminal or serial port control mode, pressing this
key will trigger E015 alarm and the drive will coast
to stop.
STOP/RESET can be used to reset a fault in all
control mode.
Ten's place: reserved
Hundred's place: lock up keypad selection
You can select to lock all or part of the keys.
0: not lock the keypad.
1: lock all keys on the keypad.
2: lock all keys on the keypad except
STOP/RESET key.
3: lock all keys on the keypad except
4: lock all keys on the keypad except RUN and
STOP key.
Keypad locking method: press FUNC/DATA key
and PRG key at the same time for 3 seconds.
Unlocking method: press FUNC/DATA key and
hold it, press ▼ key three times (within 3
seconds).
F9.08 Reserved
F9.09 Acc/Dec time unit Range: 0, 1 【0】
0: second
1: minute
It is valid for all acceleration or deceleration
except jog and traversing operation.
The Acc/Dec time can be as long as 60 hours.
Note:
It is recommended to select Second as time unit.
F9.10 Droop control
The function applies to the occasion that many
drives control a single load for equalizing power
distribution. As Fig. 5-64 shows, 5 drives are
driving a conveyer of 5 motors.
key.
Range: 0.00 ~ 10.00Hz
【 0.00Hz 】