Para.
Name
Motor
FL.00
overload
protection
Motor
overload
FL.01
protection
factor
Stall over
FL.02
voltage
Stall over
FL.03
voltage point
Overload
detection
config
FL.04
Group FL: Protection Parameters
0: disabled
1:Common motor (with low speed compensation)
2: Variable frequency motor (without low speed
compensation)
20.0 ~ 110.0 %
0: disabled (when braking resistor installed)
1: enabled
380V: 120.0 ~ 150.0 %
220V: 110.0 ~ 130.0 %
One's place of FL.04: overload detection mode
0: the detection is done as long as the drive is
operating.
1: the detection is done only when the drive
works at constant speed.
Ten's place of FL.04: action mode
0: The overload is ignored, no alarm.
1: During "Overload Alarm Effective Period",
the drive will alarm and stop operation.
Hundred's place of FL.04: reference current
0: the overload detection threshold (FL.05) is
set based on motor's rated current. Fault
code E014.
1: the overload detection threashold (FL.05)
is set based on drive's rated current. Fault
code E013.
EV1000 Series General Purpose Variable Speed Drive User Manual
Range
Appendix 1 Parameter Set
Unit
Default
1
1
0.1 %
100.0 %
1
1
140.0 %
0.1 %
120.0 %
1
000
129
Modification
×
×
×
×
×