Note:
1. Wrong parameter setting can cause overheating of
the motor or triggers the over-current protection of the
drive.
2. Refer to F0.21 for definition of fz.
3. When using synchron motor, you should select
manual torque boost, and adjust V/F curve according
to the motor parameters and application.
F0.10 Acc time 1
F0.11 Dec time 1
output
frequency
f
max
t
1
Fig. 5-4 Acc/Dec time definition
Acc time is the time taken for the motor to
accelerate from 0 Hz to the maximum frequency
(as set in F0.05), see t
Dec time is the time taken for the motor to
decelerate from maximum frequency (F0.05) to 0
Hz, see t
in Fig. 5-4.
2
EV1000 has four pair of acc/dec time. Here we
only introduce acc/dec 1. Please find acc/dec
time 2~4 in section 5.4: F3.17~F3.22.
Hint:
The unit of acc/dec 1~4 can be selected by F9.09, the
options are: minute, second. The default is second.
F0.12 Upper limit of
freq.
F0.13 Lower limit of
frequency
Please refer f
and f
H
Range: 0.1~3600s(min)【6.0s】
Range: 0.1~3600s(min)【6.0s】
t
2
in Fig. 5-4.
1
Range: upper limet ~max. output
frequency【50.00Hz】
Range: 0~upper limet of frequency
【0.00Hz】
in Fig. 5-2.
L
EV1000 Series General Purpose Variable Speed Drive User Manual
Note:
It is possible for the actual output frequency to
fluctuate within ±2.5Hz in the bus-voltage control
process.
F0.14 V/F curve setting
F0.15 V/F freq. F3
F0.16 V/F voltage V3
F0.17 V/F freq. F2
F0.18 V/F voltage V2
F0.19 V/F freq. F1
F0.20 V/F voltage V1
This group of parameters defines the V/F setting
modes so as to satisfy the requirements of
time
different loads. Three fixed curves and one
user-defined curve can be selected according to
the setting of F0.14.
If F0.14 is set to 1, a 2-order curve is selected, as
shown in Fig. 5-5 as curve 1;
If F0.14 is set to 2, a 1.7-order curve is selected,
as shown in Fig. 5-5 as curve 2;
If F0.14 is set to 3, a 1.2-order curve is selected,
as shown in Fig. 5-5 as curve 3;
The above V/F curves are suitable for the
variable-torque loads such as fan & pumps. The
user can select the curves according to the actual
load so as to achieve the best energy-saving
effects.
Chapter 5 Parameters
Range: 0~3【0】
Range: F0.17~F0.06【0.00Hz】
Range: F0.18~100.0%【0.0%】
Range: F0.19~F0.15【0.00Hz】
Range: F0.20~F0.16【0.0%】
Range: 0~F0.17【0.00Hz】
Range: 0~F0.18【0.0%】
37