24
Chapter 3 Installation and Wiring
Category Terminals
VRF
Power
supply
GND
Others
TA/TB/TC
1)Analog Input Terminal Wiring
① Terminal VCI receives analog voltage input,
the wiring diagram is as follows:
0~+10V
Shield layer near the drive
is grounded
Fig. 3-9 VCI Wiring Diagram
② Terminal CCI receives analog signal. Select
current or voltage signal by setting jumper. Refer
to the figure below:
0 ~ +10V
or 0/4 ~
20mA
Shield near the drive is
connected to the PE
Fig. 3-10 CCI Wiring Diagram
2)Analog Output Terminal Wiring
If the analog output terminal AO1 and AO2 are
connected with analog meter, it can measure
many parameters. The jumpers for AO1 and AO2
are CN16 and CN17.
Name
+10V power
Provide +10V power supply
supply
GND of +10V
reference ground of analog signal and 10V
power supply
power supply
TA, TB and TC can be defined as
Relay output
multi-functional digital output signals. Please
refer to Section 5.8.
EV1000
VRF(+10V)
VCI
GND
EV1000
PV Series
CCI current
VRF(+10V)
CCI
CCI voltage
GND
PE
CN10
EV1000 Series General Purpose Variable Speed Drive User Manual
Function
EV1000
PV Series
Fig. 3-11 Analog Output Terminal Wiring
PE
Hint:
1. When using analog input, you should install
capacitor-filter or common-mode inductor between
VCI and GND, or between CCI and GND.
2. Analog I/O signals are sensible to interference,
ensure to use shielded cable and ground it properly.
The cable length should be as short as possible.
3)Serial Communication Port Connection
The drive can be connected to the host with
I
RS485 port directly.
V
Fig. 3-9 shows the connection of the drive with
the host with RS232 port.
I
V
Fig. 3-13 shows the connection of the drive to
PROFIBUS system via TDS-PA01 PROFIBUS
adapter.
Using above wiring method, you can build a
"single-master single slave" system or a
"single-master multi-slaves" system. The drives in
the network can be monitored, and be controlled
remotely and automatically in real time by using a
PC or PLC controller. Thus more complicated
operation control can be realized.
Specification
Output: +10V,
Setpoint accuracy: ±10%
Max. output current: 100mA
TA-TB: normally closed;
TA-TC: normally open
Contact capacity: 250VAC/2A
(COSφ=1), 250VAC/1A
(COSφ=0.4), 30V
analog
meter
AO1
AO2
GND
AO1:CN16;AO2:
CN17
/1A
DC
analog current
output
0/4-20mA
0/2-10V
anlog voltage
output
0/4-20mA
0/2-10V