Chapter 5 Parameters
between jog (F3.14), f
Actual jog Acc and Dec time are calculated by the
formula below:
F3.13×F3.15
t
=
1
F0.05
F3.13× F3.16
t
=
3
F0.05
f
Frequency
1
t
t
1
Jog command
Fig. 5-18 Jog Parameters Illustration
Interval of Jog operation (F3.14) is the period
between two executed jog commands. The jog
command sent during the interval is invalid, and
the drive continues to operate at zero frequency.
If this command exist until the end of the interval,
it will be executed.
Note:
1. In Jog operation process, the drive starts according
to starting mode 0 and stops according to stopping
mode 0. The unit of Acc/Dec time is second.
2. Jog operation can be controlled by terminals and
serial port.
F3.17 Acc time 2
F3.18 Dec time 2
F3.19 Acc time 3
F3.20 Dec time 3
F3.21 Acc time 4
F3.22 Dec time 4
Three kinds of Acc/Dec time can be defined, and
the drive's Acc/Dec time 1~4 can be selected by
is jog frequency (F3.13).
1
t
3
t
4
2
Jog command
Range: 0.1~3600s(min) 【6.0s】
Range: 0.1~3600s(min) 【6.0s】
Range: 0.1~3600s(min) 【6.0s】
Range: 0.1~3600s(min) 【6.0s】
Range: 0.1~3600s(min) 【6.0s】
Range: 0.1~3600s(min) 【6.0s】
EV1000 Series General Purpose Variable Speed Drive User Manual
different combinations of control terminals, refer
to F7.00~F7.07 for the definitions of terminals
used to select Acc/Dec time.
Note:
Acc time 1 and Dec time 1 is defined in F0.10 and
F0.11 respectively.
F3.23 MS Freq.1
F3.24 MS Freq. 2 Range: Lower limit~upper limit
F3.25 MS Freq. 3 Range: Lower limit~upper limit
Time
F3.26 MS Freq. 4 Range: Lower limit~upper limit
F3.27 MS Freq. 5 Range: Lower limit~upper limit
Time
F3.28 MS Freq. 6 Range: Lower limit~upper limit
F3.29 MS Freq. 7 Range: Lower limit~upper limit
These frequencies will be used in simple PLC
operation and multi-speed operation, refer to the
introductions of F7.00~F7.07 and group F4
parameters.
F3.30 Skip freq.
F3.31 Skip freq. 1
range
F3.32 Skip freq. 2
F3.33 Skip freq. 2
range
F3.34 Skip freq. 3
F3.35 Skip freq. 3
range
Range: Lower limit~upper limit
【5.00Hz】
【10.00Hz】
【20.00Hz】
【30.00Hz】
【40.00Hz】
【45.00Hz】
【50.00Hz】
Range: 0.00~650.00Hz
【0.00Hz】
Range: 0.00~30.00Hz
【0.00Hz】
Range: 0.00~650.00Hz
【0.00Hz】
Range: 0.00~30.00Hz
【0.00Hz】
Range: 0.00~650.00Hz
【0.00Hz】
Range: 0.00~30.00Hz
【0.00Hz】