Upper limit of
freq. F
H
Central Freq. Fset
Lower limit of freq. F
Preset freq.
Run
command
stop
command
The central frequency is the frequency of simple operation, MS running or PLC.
The traverse is invalid for jog or close-loop running.
When both PLC and traverse are enabled, the traverse is invalid when transferring to another PLC stage.
The output frequency begins to traverse after arriving at the PLC preset frequency within Acc/Dec time.
When receiving Stop command, the drive will stop according to PLC Dec time.
F6.00 Traverse function
selection
0: disabled
1: enabled
F6.01 Traverse mode
This parameter is to set the operating mode of
traverse. Refer to the figure below.
Freq. (Hz)
Traverse amplitude Aw=Fset*F6.04
+ Aw
- Aw
a1
L
Step freq.=AW*F6.05
a1
Waiting time
Accelerate
F6.03
according
to Acc time
Fig. 5-36 Traverse Operation
Range: 0 ~ 1 【0】
Range: 0000 ~ 1111 【0000】
EV1000 Series General Purpose Variable Speed Drive User Manual
Rising
time=F6.06*F6.07
Traverse
operating
cycle
Thou
Hun
Ten One
Start mode
0: auto
1: terminal config. (manually)
Amplitude
0: varied(based on central freq.)
1: fixed (based on max. freq.)
Restart mode
0: start to the state before power-off
1: restart, no other requirement
Save traverse state upon power failure
0: save
1: not save
Fig. 5-37 Traverse Mode Setting
One's place of F6.01: transfer mode
0: auto
The drive will stay at traverse preset frequency
(F6.02) for a period of time (F6.03), and then
begin traverse automatically.
1: terminal configuration (manually)
When multi-function terminal is enabled and the
Chapter 5 Parameters
t
Decelerate
according
to Dec time
53