Emerson EV1000-2S0004G User Manual page 40

Ev1000 series general purpose variable speed drive
Hide thumbs Also See for EV1000-2S0004G:
Table of Contents

Advertisement

艾默生变频器、艾默生CT高级授权代理商--广州盟雄 020-85543394 qq:2294731312
36
Chapter 5 Parameters
the drive.
1: Terminal control: Input operating commands
via terminals
Use terminals FWD, REV, to start and stop the
drive.
2: Serial port control: Input operating commands
via serial port
Use serial port to start and stop the drive.
Note:
Note that during operating process, the control modes
can be changed by changing the setting of F0.03. Be
careful if you want to do so.
F0.04 Running Direction
The function applies to keypad control and serial
port control, but not terminal control mode.
0: Forward
F0.05 Max. output
frequency
F0.06 Base frequency Range: 1.00~650.00Hz 【50.00Hz】
F0.07 Max. output
voltage
The max. frequency refers to the allowed max.
output frequency of the drive. Refer to the f
Fig. 5-2;
Base frequency normally corresponds with the
rated frequency of the motor. It is the Min
frequency when the drive outputs the highest
voltage, as shown in Fig. 5-2 as f
Max output voltage is the drive's output voltage
when the drive outputs base frequency, as shown
in Fig. 5-2 as V
max.
voltage of the motor.
Range: 0, 1
1: Reverse
Range: Max {50.00, F0.12 upper
limit}~650.00Hz【50.00Hz】
Range: 1~480V 【drive's rated】
b
This corresponds to the rated
EV1000 Series General Purpose Variable Speed Drive User Manual
V
max
Fig. 5-2 Characteristic Parameters Definition
The f
and f
H
upper limit and lower limit of frequency
respectively.
【0】
Note:
Please set fmax, fb and Vmax according to motor
parameters on its nameplate. Failing to do so may
damage the motor.
F0.08 Reserved
F0.09 Torque boost
In order to compensate the torque drop at low
frequency, the drive can boost the voltage so as
to increase the torque. If F0.09 is set to 0, auto
torque boost is enabled and if set at non-zero,
manual torque boost is enabled, as shown in Fig.
5-3.
in
max
output
voltage
V
max
V
b
Vb:manual torque boost
fz:cut-off freq. for torque boost
fb:basic operating freq.
Fig. 5-3 Torque boost (shadow area: boost value)
output
voltage
f
f
f
L
b
H
are defined by F0.12 and F0.13 as
L
Range: 0~30.0%【0.0%】
f
f
z
b
Vmax:Max output voltage
output
frequency
f
max
output
freq.

Hide quick links:

Advertisement

Table of Contents
loading