艾默生变频器、艾默生CT高级授权代理商--广州盟雄 020-85543394 qq:2294731312
98
Appendix 1 Parameter Set
Para.
Name
F4.00 Simple PLC mode
Group 4: PLC Parameters
One's place of F4.00, PLC running mode selection
0: Disabled
1: stop after a single cycle
2: Maintain value of the last stage after 1 cycle
3: continuous cycle
Ten's place of F4.00: Restart mode after PLC interruption
0: start from the first stage
1: continue from the stage frequency where the drive stops
2: Start from the frequency where it stops
Hundred's place of F4.00: Save PLC state after poweroff
0: not save
1: save
Thousand's place: Selection of time unit
0: Second
1: Minute
EV1000 Series General Purpose Variable Speed Drive User Manual
Range
Unit Default Modification
1
0000
×