艾默生变频器、艾默生CT高级授权代理商--广州盟雄 020-85543394 qq:2294731312
Precautions for communication port connection:
The PE terminal of each drive should be
earthed at a nearby grounding point;
The GND terminal of each drive should be
connected together;
RS485 communication uses shielded cables,
which is earthed at one side. The earth wire of
the shielded cable is connected to RS485
communication module (PE).
If the above standard wiring methods cannot
meet the requirements, you can take the actions
below:
Use isolated RS485 communication module;
If the noise is transmitted through the GND
line to the drive or other devices, which
results in malfunction of them, you may
disconnect the GND lines.
4)Multi-function Input Terminal and FWD, REV
EV 1000
RS485 port
Function
terminal
RS485 -
RS485 +
Fig. 3-12 RS485-(RS485/RS232)-RS232 communication cable
EV1000
RS485 port
Func
Terminal
signal-Func
RS485-
signal+ Func
RS485+
EV2000
TD3000
Fig. 3-13 RS485-(TDS-PA01)-PROFIBUS Wiring Diagram
EV1000 Series General Purpose Variable Speed Drive User Manual
RS485/RS232
converter
Function
Terminal
5V power
+ 5V
Transmit
TXD
Receive
RXD
Ground
GND
Terminal
Function
RS485 -
RS485 +
TDS-PA01
fieldbus
Func
Terminal
Twisted
RS485-
cable
RS485+
TDS-PA01
TDS-PA01
Wiring
The multi-function input terminals use full-bridge
rectifying circuit, as the below figure shows. PLC
is the common terminal for X1~X5, FWD and
REV. The PLC terminal can sink or source current.
Wire connections X1~X5, FWD and REV is
flexible and the typical wiring is shown below:
① Connection method 1
It is default to use the drive's internal power
source 24V, i.e. PLC connected with P24.
If you want to use external power supply, make
sure to remove the wire between PLC and P24.
Chapter 3 Installation and Wiring
Sign-a
Pin
shielded
l
cable
Enclo-
PE
sure
RXD
2
TXD
3
GND
5
DTR
4
DSR
6
RI
9
CD
1
RTS
7
CTS
8
Connect to
PROFIBUS
A
B
Be able to connect
1-32 RS485