time will be saved when poweroff, and the drive
will start according to the setting of ten's place of
F4.00 after powerup.
Thousand's place: Selection of time unit
0: Second
1: Minute
This unit is only valid for defining the PLC
operating time. The unit of Acc/Dec time in PLC
operation is determined by F9.09.
Note:
1. A stage is ineffective if its run time is set to 0.
2. You can use terminals to pause and disable PLC
operation, and clear the memorized parameters. See
F7 parameters.
F4.01 Stage 1 setting
F4.02 Stage 1 run time Range: 0 ~ 6500s (min) 【 20.0s 】
F4.03 Stage 2 setting
F4.04 Stage 2 run time Range: 0 ~ 6500s (min) 【 20.0s 】
F4.05 Stage 3 setting
F4.06 Stage 3 run time Range: 0 ~ 6500s ( min ) 【 20.0s 】
F4.07 Stage 4 setting
F4.08 Stage 4 run time Range: 0 ~ 6500s (min) 【 20.0s 】
F4.09 Stage 5 setting
F4.10 Stage 5 run time Range: 0 ~ 6500s (min) 【 20.0s 】
F4.11 Stage 6 setting
F4.12 Stage 6 run time Range: 0 ~ 6500s(min) 【 20.0s 】
F4.13 Stage 7 setting
F4.14 Stage 7 run time Range: 0 ~ 6500s (min) 【 20.0s 】
F4.01, F4.03, F4.05, F4.07, F4.09, F4.11 and
F4.13 are to set frequency, direction, Acc/Dec
time of PLC stages. See Fig. 5-27:
Range: 000 ~ 323 【000】
Range: 000 ~ 323 【 000 】
Range: 000 ~ 323 【000】
Range: 000 ~ 323 【 000 】
Range: 000 ~ 323 【 000 】
Range: 000 ~ 323 【000】
Range: 000 ~ 323 【000】
EV1000 Series General Purpose Variable Speed Drive User Manual
T
H
Ten One
0: Preset frequency i
2: Preset close-loop reference i
Running direction selection
1: Reverse
2: Determined by running
Fig. 5-27 PLC Stage i setting(i=1~7)
One's place:
0: select MS frequency i, e.g. i=3, means the
frequency for stage 3 is MS frequency 3, see
F3.23~F3.29.
1: the frequency is determined by F0.00
2: MS close loop setting I, e.g. i=2, the frequency
of stage 2 is MS close loop setting 2. See F5.20
~F5.26.
3: Determined by F5.01.
PLC can realize close-loop operation in a certain
stage. Close-loop reference selectors can be
preset close-loop reference I or determined by
parameter F5.01; and the feedback is determined
by F5.02. When the setting method is determined
by F5.01, the terminals can be selected via
close-loop input. See F7.00~F7.07 and
F5.20~F5.26 for details
Note:
When the PLC operating direction is determined by
operating commands, the motor's operating direction
can be changed by external command. For example,
Running forward can be ordered by terminal
FWD-COM. The direction is decided by running
command and if it cannot be determined, the drive
will runs in the direction of last operating stage.
Chapter 5 Parameters
Frequency setting
1: Determined by F0.00
3: Determined by F5.01
0: Forward
command
Acc/Dec time selection
0: Acc/Dec 1
1: Acc/Dec 2
2: Acc/Dec 3
3: Acc/Dec 4
Reserved
47