Table 3-3 Specifications - Toshiba G9000 SERIES Installation And Operation Manual

480/480 v 1000/1330/1500/1660/2000kva
Hide thumbs Also See for G9000 SERIES:
Table of Contents

Advertisement

Rated Output kVA
Rated Output kW
AC INPUT
Configuration
Voltage
Frequency
Reflected Current THD
Walk-In Function
STATIC BYPASS INPUT
Configuration
Voltage
Frequency
BATTERY
Type
Ride Through
Nominal Voltage
Minimum Voltage
Float Voltage
Number of Cells
Maximum Recharge Current
DC-AC Efficiency
AC OUTPUT
Configuration
Voltage
Voltage Regulation
Frequency
Frequency Regulation
Power Factor
Power Factor Range
Voltage THD
Transient Response
Transient Recovery Time
Voltage Unbalance
Phase Displacement
Inverter Overload
Bypass Overload
ENVIRONMENTAL**
Cooling
Operating Temperature
Relative Humidity
Altitude
Location
Audible Noise (Typical)
Paint Color
Clearance Required
**Indication that the unit is intended for installation in a temperature-regulated,
indoor area that is relatively free of conductive contaminants.
G9000 1000-2000kVA Installation and Operation Manual 91469-007
Table 3–3 Specifications
1000
1330
1000
1330
1-30 Seconds (in 1 second increments)
200 A
266 A
±1% (Balanced Load), ±2% (Unbalanced Load)
0.7 Lagging to 0.8 Leading (within output kW rating)
2% maximum THD at 100% linear load
5% maximum THD at 100% non-linear load
±2% maximum at 100% load step
±1% maximum at loss/return of AC power
±5% maximum at load transfer to/from static bypass
2% maximum at 100% unbalanced load
Recommended : 68゚F to 86゚F ( 20゚C to 30゚C)
0 to 6500 feet No Derating at 104゚F (40゚C)
Indoor (free from corrosive gases and dust)
71dB
72dB
Sides: 0 in. (0 mm) with cabinets installed aside, otherwise 1 in. (25 mm)
1500
1500
3 phase, 3 wire
480 V +15% to -20%
60 Hz ±10%
3% typ. at 100% load
3 phase, 3 wire
480 V ±10%
60 Hz ±5%
Lead Acid, Wet Cell
Application Specific
480 Vdc
400 Vdc
Programmable up to 545 VDC
240
300 A
>96%
3 phase, 3 wire
480 V
60 Hz
±0.01% in free running mode
Unity (nominal)
Less than 20ms
1 deg. maximum at 100% Load
125% for 10 minutes
150% for 60 seconds
500% for 1 cycle
(with bypass available)
Forced Air
32゚F to 104゚F (0゚C to 40゚C).
5% – 95% Non-Condensing
73dB
Munsell N1.5 (Black)
Top : 23.6 in. (600 mm)
Front : 39.4 in. (1000 mm)
Rear : 0 in. (0 mm)
1660
2000
1660
2000
332 A
400 A
73dB
74dB
19

Advertisement

Table of Contents
loading

Table of Contents