Table 3-4 Rating Of Contactors, Breakers, And Fuses; Table 3-5 Ac-Ac Efficiency Specifications - Toshiba G9000 SERIES Installation And Operation Manual

480/480 v 1000/1330/1500/1660/2000kva
Hide thumbs Also See for G9000 SERIES:
Table of Contents

Advertisement

Table 3–4 Rating of Contactors, Breakers, and Fuses
DEVICE
NUMBER
CB1
AC input contactor
CB2
CB3
52C
52S
88RC
Battery disconnect
User supply
User supply
Bypass input breaker
User supply
FP, FC, FN
FBP, FBN
FBR1, FBR2, FBR3
FBR, FBS, FBT
Control power fuse
FBO1, FBO2, FBO3
FOA, FOB, FOC
FIA, FIB
Control power fuse
FUA, FUB, FUC
(OPTION)
Bypass input fuse
FSU, FSV, FSW
Rated Output
Power
1000kVA / 1000kW
1330kVA / 1330kW
1500kVA / 1500kW
1660kVA / 1660kW
2000kVA / 2000kW
*Tentative values approximated from 2000kVA Testing
20
1000kVA 1330kVA 1500kVA 1660kVA 2000kVA
APPLICATION
1000kW
Battery contactor
STS contactor
452A
Inverter output
452A
contactor
Bypass contactor
1278A
Control circuit
20A
contactor
breaker
(Recommended)
AC input breaker
(Recommended)
(Recommended)
DC fuse
DC fuse
2000A/550V
Table 3–5 AC-AC Efficiency Specifications
25% Load
50% Load
96.30%
97.00%
96.08%*
96.98%*
96.08%*
96.98%*
96.08%*
96.98%*
96.08%
96.98%
G9000 1000-2000kVA Installation and Operation Manual 91469-007
OUTPUT CAPACITY OF EQUIPMENT
1330kW
1500kW
452A
285A
1992A
See Appendix A: Installation Planning Guide
See Appendix A: Installation Planning Guide
See Appendix A: Installation Planning Guide
315A / 690V
1000A / 600V
12A / 600V
12A / 600V
800A / 650V
75% Load
97.10%
96.85%*
96.85%*
96.85%*
96.85%
1660k W
2000kW
704A
452A
2843A
20A
3600A / 550V
100% Load
96.80%
96.62%*
96.62%*
96.62%*
96.62%