Use Ethernet STP (Shielded Twisted Pair) Cable (Cat 6) with shielded RJ45 modular connectors
for all communication cabling.
Use of UTP (Unshielded Twisted Pair) Cable may cause malfunction.
Total cable length from UPS-1 to UPS-n should be within 100m (330ft).
UPS-1
IFAU-16A
CN961 DIAIN
CN962 DIBIN
CN963 DIAOUT
CN964 DIBOUT
CN941 CAIN
CN942 CBIN
CN943 CAOUT
CN944 CBOUT
CN951 TLAIN
CN952 TLBIN
CN953 TLAOUT
CN954 TLBOUT
UPS-1
1 to 8: ON
(All ON)
Figure 5-8 Detail of IFAU-16A Control Wire Connections for N units in MMS Configuration
Table 5–7 S
48
UPS-2
IFAU-16A
CN961 DIAIN
CN962 DIBIN
CN963 DIAOUT
CN964 DIBOUT
CN941 CAIN
CN942 CBIN
CN943 CAOUT
CN944 CBOUT
CN951 TLAIN
CN952 TLBIN
CN953 TLAOUT
CN954 TLBOUT
UPS-2 ~ UPS-(n-1)
1 to 8: OFF
(All OFF)
tatus of Jumpers on Parallel Interface Board (IFAU-16A)
#
Device
1
JP1
2
JP6
3
JP11
G9000 1000-2000kVA Installation and Operation Manual 91469-007
CN961 DIAIN
CN962 DIBIN
CN963 DIAOUT
CN964 DIBOUT
CN941 CAIN
CN942 CBIN
CN943 CAOUT
CN944 CBOUT
CN951 TLAIN
CN952 TLBIN
CN953 TLAOUT
CN954 TLBOUT
UPS-n
1 and 2: ON
3 to 8: OFF
Status
SHORT
SHORT
OPEN
UPS-n
IFAU-16A