Aux Contacts - Output; Figure 4-18 Control Wiring For Aux Output Contacts; Figure 4-19 External Signal Output Terminal Block (With Default Settings) - Toshiba G9000 SERIES Installation And Operation Manual

480/480 v 1000/1330/1500/1660/2000kva
Hide thumbs Also See for G9000 SERIES:
Table of Contents

Advertisement

4.4.2

Aux Contacts - Output

The Output terminal provides eight (OUT1 thru OUT8) form "A" NO (Normally Open) dry type
programmable contacts to drive annunciation signals sourced or "wetted" by external
monitoring devices. All output contacts are rated for NEC Class 2 operation (30VDC /
1ADC.)
The output dry contacts should be operated at their rated values or lower. Figure 4-18
illustrates a typical installation. The external relay can be a lamp, LED, computer, etc.
External block IOAU-19
UPS Cabinet
Relay
Contact

Figure 4-18 Control Wiring for Aux Output Contacts

TN21-25
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
UPS
NOTE: Summary Alarm; activated when a major fault has occurred with the system.

Figure 4-19 External Signal Output Terminal Block (with default settings)

G9000 1000-2000kVA Installation and Operation Manual 91469-007
Terminal
Terminal
Wire Size: #14AWG
2
(2 mm
) or less
NEC Class 2
Power Source
User supplied
TN21-25
1-2
SUMMARY ALARM
3-4
OUT1: LOAD ON BYPASS
5-6
OUT2: LOAD ON INVERTER
7-8
OUT3: BATTERY OPERATION
9-10
OUT4: CONVERTER OPERATION
11-12
OUT5: BATTERY LOW VOLTAGE
13-14
OUT6: OVERLOAD
15-16
OUT7: SPARE
17-18
OUT8: TOTAL ALARM
52C CLOSE
19-20
* Relay contactor (52C close): Normally Closed
External to
UPS Cabinet
Relay
Coil
Setting