Diagnosis and troubleshooting
r958
15 14 13 12 11 10
Fault/error display
6-8
Alarms A081 and A088 are also stored for information purposes in
alarm parameter 6 (r958). The individual alarms are assigned to the
corresponding bits in r958 (Bit x = 1: alarm present):
9
8
7
A second CB uses the bits 8 to 15 of r958 and the warnings A089 to
A096.
When the CBL is combined with the control/technology board (CU/TB),
the following fault messages may occur:
Fault
F 080
TB/CB Init.:
Incorrect initialization and parameterization of the CBL via the
dual-port RAM interface (DPR interface)
Parameterization for CBL false, cause of incorrect
parameterization in diagnostic parameter r732.01
Correct CB parameter P711-P718.
Correct CB bus address (CC-Link) P918.
CBL defective
Replace CBL
F 081
DPR heartbeat:
The CBL is no longer processing the heartbeat counter.
CBL not correctly inserted into the electronics box
Check CBL
CBL defective
Replace CBL
F 082
DPR telegram failure:
The telegram-failure time set by means of parameter P722 has
expired.
PLC (bus master) failed (green LED on the CBL is
continuously off)
Check PLC (cpu and CC-Link master)
Check cable
Connection between the bus nodes has been interrupted
(green LED on the CBL is continuously off, RUNLED, SDLED
and RDLED are continuously off)
Check the bus cable
Check PLC (CC-Link master)
EMC loading of the bus cable too high (ERRLED flashes)
Refer to EMC notes
Telegram monitoring time has been set too low (green, yellow
and red LED on the CBL flashes synchronous)
Increase the parameter value in P722
CBL defective
Replace CBL
Possible cause
Remedy
Table 6-17
Fault displays on the basic unit
6
5
4
3
2
1
Meaning
6SE7087-6NX84-0GB0
Operating Instructions
03.99
0
Bit
Alarm A081
Alarm A088
Siemens AG
SIMOVERT MASTERDRIVES