Siemens SIMOVERT MASTERDRIVES Operating Instructions Manual page 23

Cbl-communication board cc-link
Hide thumbs Also See for SIMOVERT MASTERDRIVES:
Table of Contents

Advertisement

03.99
Device No
Signal name
RXn0
Forward operation
RXn1
Reverse operation
RXn2
Running (RUN)
RXn3
Frequency reached (SU)
RXn4
Overload (OL)
RXn5
Momentary power failure
(IPF)
RXn6
Frequency detection (FU)
RXn7
Abnormal (ABC)
RXn8
Info flag 0 (I0)
RXn9
Info flag 7 (I7)
RXnA
Info flag 15 (I15)
RXnC
Monitoring
RXnD
Frequency setting
complete (RAM)
RXnF
Command code execution
complete
RX (n+1)8
Initial data processing
request flag
RX (n+1)9
Initial data setting
complete flag
RX (n+1)A
Error status flag
RX (n+1)B
Remote ready
Siemens AG
6SE7087-6NX84-0GB0
SIMOVERT MASTERDRIVES
OFF: Other than forward operation
ON: Forward operation
OFF: Other than reverse operation
ON: Reverse operation
ON during the inverter operation
ON when output frequency is in the set frequency ± permission
deviation; refer to function diagram 480 and status word bit 8
ON when inverter overload warning is active; refer to status
word bit 22
ON when momentary power failure occurs; refer to status word
bit 11 "Low voltage fault"
ON when comparison value is reached; refer to function
diagram 480 and status word bit 10
ON when inverter protection function is activated and the output
stopped.
Additional info flag: Status word bit 0 "Ready to switch on"
Refer to chapter 4.11 "Optional flags in CBL profile"
Additional info flag: Status word bit 7 "Warning active"
Refer to chapter 4.11 "Optional flags in CBL profile"
Additional info flag: Status word bit 15
Refer to chapter 4.11 "Optional flags in CBL profile"
ON when the monitor value is set in RWrm while the monitor
command (RYnC) is ON. It turns OFF when the monitor
command (RYnC) is turned OFF.
Refer to chapter 4.5 "Monitoring"
ON when frequency is written to the inverter while frequency
set command (RYnD) is ON. It turns OFF when the frequency
set command (RYnD) is turned OFF.
Refer to chapter 4.4 "Setpoint handling"
ON when process corresponding to command code (RWwm+2)
is executed and completed by turning ON the command code
execution request (RYnF). It turns OFF when the command
code execution request (RYnF) is turned OFF.
Refer to chapter 4.6 "Command code execution"
After power-on or new initializing the initial data processing
request flag is turned on by CBL.
Refer to chapter 4.3 "Initial process and initial data setting"
When the initial data setting request (RY(n+1)9 is ON) is
issued, it turns ON after initial data setting is completed.
Refer to chapter 4.3 "Initial process and initial data setting"
ON when the inverter has an error.
Refer to chapter 4.3 "Initial process and initial data setting"
ON after initial process or initial data setting. OFF during error
status is ON;
Refer to chapter 4.3 "Initial process and initial data setting"
Table 4-2
CC-Link Profile CBL: Bit definition
Operating Instructions
Communication via CC-Link
Description
4-3