Courier Communication - GE P741 Technical Manual

Busbar differential protection relay
Table of Contents

Advertisement

P74x/EN SC/Na7
(SC) 13-6
Note the following warnings apply:
It is extremely important that the 120Ω termination resistors are fitted. Failure to do so
will result in an excessive bias voltage that may damage the devices connected to the
bus.
As the field voltage is much higher than that required, GE cannot assume responsibility
for any damage that may occur to a device connected to the network as a result
incorrect application of this voltage.
Ensure that the field voltage is not being used for other purposes (i.e. powering logic
inputs) as this may cause noise to be passed to the communication network.
1.2.2

Courier communication

Courier works on a master/slave basis where the slave units contain information in the form
of a database, and respond with information from the database when it is requested by a
master unit.
The relay is a slave unit that is designed to be used with a Courier master unit such as S1,
S10, PAS&T or a SCADA system.
To use the rear port to communicate with a PC-based master station using Courier, a KITZ
K-Bus to EIA(RS)232 protocol converter is required. This unit is available from GE. A
typical connection arrangement is shown in Figure 2. For more detailed information on other
possible connection arrangements refer to the manual for the Courier master station
software and the manual for the KITZ protocol converter. Each spur of the K-Bus twisted
pair wiring can be up to 1000m in length and have up to 32 relays connected to it.
SC
SCADA Communications
MiCOM P741, P742, P743
of