GE P741 Technical Manual page 275

Busbar differential protection relay
Table of Contents

Advertisement

Programmable Logic
MiCOM P741, P742, P743
DDB
Relay
English Text
No.
P743
235
Current Overflow
P743
263
Dead Zone Earth
P743
261
Dead Zone Fault
P743
262
Dead Zone Phase
P743
248
Delta IA
P743
249
Delta IB
P743
250
Delta IC
P743
251
Delta IN
P743
116
Ext. 3 ph Trip
P743
122
Ext. CB Fail
P743
168
Ext. Retrip Ph A
P743
169
Ext. Retrip Ph B
P743
170
Ext. Retrip Ph C
P743
117
External Trip A
P743
118
External Trip B
P743
119
External Trip C
P743
468
Fault_REC_TRIG
P743
252
Fibre Com Error
P743
253
Fibre Com Worn
P743
470
Field Voltage Fail
P743
657
FnKey LED 1 Grn
P743
781
FnKey LED 1 Grn
P743
656
FnKey LED 1 Red
P743
780
FnKey LED 1 Red
P743
675
FnKey LED 10 Grn TRI_LED
P743
799
FnKey LED 10 Grn TRI_LED_CON
P743
674
FnKey LED 10
Red
P743
798
FnKey LED 10
Red
P743
343
Forced Mode ON
P743
676
Function Key 1
P743
685
Function Key 10
P743
351
General Alarm
P743
472
GOOSE IED
Absent
P743
512
GOOSE OUT 1
Type
Source
PSL Input Signal
Saturation
PSL Input Signal
Local Protection
PSL Input Signal
Local Protection
PSL Input Signal
Local Protection
PSL Input Signal
Saturation
PSL Input Signal
Saturation
PSL Input Signal
Saturation
PSL Input Signal
Saturation
PSL Output Signal
PSL (50BF
protection)
PSL Output Signal
PSL (50BF Backtrip
protection)
PSL Input Signal
50BF Protection
PSL Input Signal
50BF Protection
PSL Input Signal
50BF Protection
PSL Output Signal
PSL (50BF
protection)
PSL Output Signal
PSL (50BF
protection)
PSL Output Signal
PSL (50BF
protection)
FRT
PSL
PSL Input Signal
Relay Integrity
PSL Input Signal
Relay Integrity
PSL Input Signal
Relay Integrity
TRI_LED
PSL (LED)
TRI_LED_CON
Output Conditioner
TRI_LED
PSL (LED)
TRI_LED_CON
Output Conditioner
PSL (LED)
Output Conditioner
TRI_LED
PSL (LED)
TRI_LED_CON
Output Conditioner
PSL Input Signal
Commissioning
FUNCTION_KEY
PSL (Function Key)
FUNCTION_KEY
PSL (Function Key)
PSL Input Signal
Relay Integrity
PSL Input Signal
IEC 61850
GOOSEOUT
PSL
P74x/EN PL/Na7
Description
Fibre optic Maximum primary current encoding
exceeded
Fault in the dead zone on the neutral
Fault in the dead zone
Fault in the dead zone on a phase
Variation detected on phase A (not used)
Variation detected on phase B (not used)
Variation detected on phase C (not used)
Variation detected on the neutral (not used)
External 3 phase Trip
Allows external protection to initiate breaker fail (if
enabled)
50BF Backtrip order from an other protection
Retrip of phase A due to an external trip initiation
of this phase (at tBF3)
Retrip of phase B due to an external trip initiation
of this phase (at tBF3)
Retrip of phase C due to an external trip initiation
of this phase (at tBF3)
External 3 phase A Trip
Allows external protection to initiate breaker fail (if
enabled)
External 3 phase B Trip
Allows external protection to initiate breaker fail (if
enabled)
External 3 phase C Trip
Allows external protection to initiate breaker fail (if
enabled)
Trigger for the Fault Recorder
Fibre communication to the CU error
Warning: fibre communication to be changed
48V Field Voltage Failure
Programmable Function Key LED 1 Green is
energized
Assignment of signal to drive output Function Key
LED 1 Green.
This LED is associated with Function Key 1.
To drive function key LED, yellow DDB 692 and
DDB 693 must be active at the same time
Programmable Function Key LED 1 Red is
energized
Assignment of signal to drive output Function Key
LED 1 Red.
This LED is associated with Function Key 1
Programmable Function Key LED 10 Green is
energized
Assignment of signal to drive output Function Key
LED 10 Green.
This LED is associated with Function Key 10.
To drive function key LED1 yellow, DDB 710 and
DDB 711 must be active at the same time
Programmable Function Key LED 10 Red is
energized
Assignment of signal to drive output Function Key
LED 10 Red.
This LED is associated with Function Key 10
When the forced positions of the CB and the
Isolators are used (during commissioning test)
Function Key 1 is activated.
In 'Normal' mode it is high on key press and in
'Toggle' mode remains high/low on single key
press
Function Key 10 is activated.
In 'Normal' mode it is high on key press and in
'Toggle' mode remains high/low on single key
press
General Alarm
The IED is not subscribed to a publishing IED in
the current scheme
GOOSE Output 1
Allows user to control a binary signal which can be
mapped via SCADA protocol output to other
devices
(PL) 7-41
PL