Waiting Configuration - GE P741 Technical Manual

Busbar differential protection relay
Table of Contents

Advertisement

Application Notes
MiCOM P741, P742, P743
5.5

Waiting Configuration

Alarm "Config error" occurs when the configuration is incorrect:
Topology download in relay does not correspond to this relay address
(be careful to erase topology by sending a default setting file)
For CU: check the coherency of threshold:
[IDCZ>2] > [ID>1] and [ID>2] > [ID>1] and [IDNCZ>2] > [IDN>1] and [IDN>2] > [IDN>1]
P74x/EN AP/Na7
(AP) 6-29
AP