Current Differential Communications; Current Inputs - GE P741 Technical Manual

Busbar differential protection relay
Table of Contents

Advertisement

Commissioning
MiCOM P741, P742, P743
4.2.9

Current differential communications

This test verifies that the P742 or P743 relay's fibre optic communications ports used for
communications to the P741 Central Unit, are operating correctly.
A
B
C
D
1 TO 7 COMMUNICATION BOARDS
FIGURE 5: P741 REAR TERMINAL BLOCKS AND COMMUNICATION PORTS
When connecting or disconnecting optical fibres care should be taken not to look directly into
the transmit port or end of the optical fibre.
From central unit, the cell [PU CONF & STATUS, PU connected] displayed the list of
peripheral units connected to the central unit.
From peripheral unit, it is possible to check the communication with the central unit by
disconnecting the optical fibre, an alarm "Fibre Com Error" should appear.
4.2.10
Current inputs (P742, P743 only)
This test verifies that the accuracy of current measurement is within the acceptable
tolerances.
All relays will leave the factory set for operation at a system frequency of 50Hz.
If operation at 60Hz is required then this must be set in cell [SYSTEM DATA, Frequency].
Apply current equal to the line current transformer secondary winding rating to each current
transformer input of the corresponding rating in turn, see Table 1 or the external connection
diagrams for the appropriate terminal numbers, checking its magnitude using a multimeter.
The corresponding reading can then be checked in the relay's MEASUREMENTS 1 column
and value displayed recorded.
The measured current values displayed on the relay LCD or a portable PC connected to the
front communication port will either be in primary or secondary Amperes. If cell [MEASURE'T
SETUP, Local Values] is set to 'Primary', the values displayed should be equal to the applied
current multiplied by the corresponding current transformer ratio set in the 'CT and VT
RATIOS' menu column (see Table 5). If cell [MEASURE'T SETUP, Local Values] is set to
'Secondary', the value displayed should be equal to the applied current.
E
F
G
H
1
3
5
7
9
11
13
15
17
LOGICAL OUTPUT CONTACT BOARD
LOGICAL INPUT CONTACT BOARD
P74x/EN CM/Na7
J
K
L
1
1
2
2
2
3
3
4
4
4
5
5
6
6
6
7
7
8
8
8
9
9
10
10
10
11
11
12
12
12
13
13
14
14
14
15
15
16
16
16
17
17
18
18
18
POWER SUPPLY MODULE
CO-PROCESSOR BOARD
OPTIONAL BOARD
(CM) 10-19
M
N
TX
IRIG-B12x
CH1
RX
R
WindRiver
xWorks
R
20148098
TX
CH2
RX
SK6
LINK
ACTIVITY
RX
TX
P3712ENc
CM

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

P742P743

Table of Contents