“Function Keys” Menu - GE P741 Technical Manual

Busbar differential protection relay
Table of Contents

Advertisement

Settings
MiCOM P741, P742, P743
Menu Text
INTERMICOM CONF
IM1 Fallback Mode
Visible if "IM1 Cmd type" ≠ "Disabled"
When "Latched", during periods of extreme where the synchronization of a message
structure is lost or is cannot be decoded, the last good command can be maintained until a
new valid message is received
When "Default": if the synchronisation is lost, after a time period, a known fallback state
can be assigned to the command.
In this latter case, the time period will need to be set in the "IM# FrameSynTim" cell and the
default value will need to be set in "IM# DefaultValue" cell. As soon as a full valid message
is seen by the relay all the timer periods are reset and the new valid command states are
used. An alarm is provided if the noise on the channel becomes excessive
IM1 DefaultValue
Visible if "IM1 Fallback Mode" = "Default"
Sets the default value to assign to the command after a time period.
IM1 FrameSyncTim
Visible if "IM1 Fallback Mode" = "Default"
Sets the time period to assign the known default value to the relay.
IM2 to IM8 Cmd type
As IM1 Cmd Type.
Note: Setting choices ere diffrent from IM2 to IM8 (see IM1 Cmd type).
When Cmd Type is enabled, Fallback Mode is enabled.
Default values and frameSync type are settable when fallback mode selection is "latched".
1.3.11
"Function keys" menu (P741 / P743)
Available in the Central Unit P741 and the Peripheral Unit P743
Menu Text
FUNCTION KEYS
Fn. Key Status
Displays the status of each function key.
Fn. Key 1 Status
Setting to activate function key. The 'Lock' setting allows a function key output that is set to
toggle mode to be locked in its current active state.
Fn. Key 1 Mode
Sets the function key in toggle or normal mode. In 'Toggle' mode, a single key press will
set/latch the function key output as 'high' or 'low' in programmable scheme logic. This
feature can be used to enable/disable relay functions. In the 'Normal' mode the function
key output will remain 'high' as long as key is pressed.
Fn. Key 1 Label
Allows the text of the function key to be changed to something more suitable for the
application.
Fn. Key 2 to 10
Status
Setting to activate function key (see "Fn. Key 1 Status")
Default Setting
Default
Default/ Latched
1
0
20ms
10ms
Default Setting
0000000000
Unlocked
Disabled, Locked, Unlock
Toggled
Toggled, Normal
Function Key 1
Unlocked
Disabled, Locked, Unlock
P74x/EN ST/Na7
Setting Range
Min.
Max.
1
1500ms
Setting Range
Min.
Max.
(ST) 4-37
Step Size
ST
1
10ms
Step Size

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

P742P743

Table of Contents