Danfoss AAF00x Operating Instructions Manual page 91

Vlt active filter
Hide thumbs Also See for AAF00x:
Table of Contents

Advertisement

General Specifications
Digital inputs:
Programmable digital inputs
Terminal number
Logic
Voltage level
Voltage level, logic'0' PNP
Voltage level, logic'1' PNP
Voltage level, logic '0' NPN
Voltage level, logic '1' NPN
Maximum voltage on input
Input resistance, R
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
*) Terminals 27 and 29 can also be programmed as output.
Control card, RS-485 serial communication:
Terminal number
Terminal number 61
The RS-485 serial communication circuit is functionally seated from other central circuits and galvanically isolated from the
supply voltage (PELV).
8
8
Digital output:
Programmable digital/pulse outputs
Terminal number
Voltage level at digital/frequency output
Max. output current (sink or source)
1) Terminal 27 and 29 can also be programmed as input.
Control card, 24 V DC output:
Terminal number
Max. load
The 24V DC supply is galvanically isolated from the supply voltage (PELV), but has the same potential as the analog and digital
inputs and outputs.
Surroundings:
Vibration test
Relative humidity
Aggressive environment (IEC 60068-2-43) H
Test method according to IEC 60068-2-43 H
Ambient temperature
- with derating
- with full output current (short temperature overload)
- at full continuous output current (24 hours)
Minimum ambient temperature during full-scale operation
Minimum ambient temperature at reduced performance
Temperature during storage/transport
Maximum altitude above sea level without derating
Maximum altitude above sea level with derating
EMC standards, Emission
EMC standards, Immunity
Control card performance:
Scan interval
90
VLT Active Filter AAF 00x
i
S test
2
S (10 days)
2
MG.90.V2.02 - VLT® is a registered Danfoss trademark
5% - 95%(IEC 721-3-3; Class 3K3 (non-condensing) during operation
EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
2 (4)
*
18, 19, 27
, 29
PNP or NPN
0 - 24V DC
< 5V DC
> 10V DC
> 19V DC
< 14V DC
28V DC
approx. 4kΩ
68 (P,TX+, RX+), 69 (N,TX-, RX-)
Common for terminals 68 and 69
27, 29
0 - 24V
40mA
: 200mA
1.0 g
class kD
max. NA° C
max. 45° C
max. 40° C
- 10°C
-25 to +70°C
1000m
3000m
EN 61800-3, EN 61000-6-1/2,
: 5ms
*
2
1)
13
0°C

Advertisement