2.2 SPECIFICATIONS
RATE OF CHANGE OF FREQUENCY
df/dt trend:
df/dt pickup level:
df/dt dropout level:
df/dt level accuracy:
Overvoltage supv.:
Overcurrent supv.:
2
Pickup delay:
Reset delay:
Time accuracy:
95% settling time for df/dt: < 24 cycles
Operate time:
BREAKER FAILURE
Mode:
Current supervision:
Current supv. pickup:
Current supv. dropout:
Current supv. accuracy:
0.1 to 2.0  CT rating: ±0.75% of reading or ±2% of rated
above 2  CT rating:
BREAKER ARCING CURRENT
Principle:
Initiation:
Compensation for auxiliary relays: 0 to 65.535 s in steps of 0.001
Alarm threshold:
Fault duration accuracy: 0.25 of a power cycle
Availability:
BREAKER FLASHOVER
Operating quantity:
Pickup level voltage:
Dropout level voltage:
Pickup level current:
Dropout level current:
Level accuracy:
Pickup delay:
Time accuracy:
Operate time:
BREAKER RESTRIKE
Principle:
Availability:
Pickup level:
Reset delay:
2-14
increasing, decreasing, bi-directional
0.10 to 15.00 Hz/s in steps of 0.01
96% of pickup
80 mHz/s or 3.5%, whichever is greater
0.100 to 3.000 pu in steps of 0.001
0.000 to 30.000 pu in steps of 0.001
0 to 65.535 s in steps of 0.001
0 to 65.535 s in steps of 0.001
±3% or ±4 ms, whichever is greater
typically 6.5 cycles at 2  pickup
typically 5.5 cycles at 3  pickup
typically 4.5 cycles at 5  pickup
1-pole, 3-pole
phase, neutral current
0.001 to 30.000 pu in steps of 0.001
97 to 98% of pickup
(whichever is greater)
±2.5% of reading
2
accumulates breaker duty (I
t) and mea-
sures fault duration
programmable per phase from any Flex-
Logic operand
0 to 50000 kA2-cycle in steps of 1
1 per CT bank with a minimum of 2
phase current, voltage and voltage differ-
ence
0 to 1.500 pu in steps of 0.001
97 to 98% of pickup
0 to 1.500 pu in steps of 0.001
97 to 98% of pickup
±0.5% or ±0.1% of rated, whichever is
greater
0 to 65.535 s in steps of 0.001
±3% or ±42 ms, whichever is greater
<42 ms at 1.10  pickup at 60 Hz
detection of high-frequency overcurrent
condition ¼ cycle after breaker opens
one per CT/VT module (not including 8Z
modules)
0.1 to 2.00 pu in steps of 0.01
0.000 to 65.535 s in steps of 0.001
D60 Line Distance Protection System
2 PRODUCT DESCRIPTION
SYNCHROCHECK
Max voltage difference: 0 to 400000 V in steps of 1
Max angle difference:
0 to 100
Max freq. difference:
0.00 to 2.00 Hz in steps of 0.01
Hysteresis for max. freq. diff.: 0.00 to 0.10 Hz in steps of 0.01
Dead source function:
None, LV1 & DV2, DV1 & LV2, DV1 or
DV2, DV1 xor DV2, DV1 & DV2
(L = Live, D = Dead)
AUTORECLOSURE
Two breakers applications
Single- and three-pole tripping schemes
Up to 4 reclose attempts before lockout
Selectable reclosing mode and breaker sequence
PILOT-AIDED SCHEMES
Direct Underreaching Transfer Trip (DUTT)
Permissive Underreaching Transfer Trip (PUTT)
Permissive Overreaching Transfer Trip (POTT)
Hybrid POTT Scheme
Directional Comparison Blocking Scheme
Directional Comparison Unblocking Scheme (DCUB)
TRIP OUTPUT
Collects trip and reclose input requests and issues outputs to con-
trol tripping and reclosing.
Communications timer delay: 0 to 65535 s in steps of 0.001
Evolving fault timer:
0.000 to 65.535 s in steps of 0.001
Timing accuracy:
±3% or 4 ms, whichever is greater
POWER SWING DETECT
Functions:
Power swing block, Out-of-step trip
Characteristic:
Mho or Quad
Measured impedance:
Positive-sequence
Blocking / tripping modes: 2-step or 3-step
Tripping mode:
Early or Delayed
Current supervision:
Pickup level:
0.050 to 30.000 pu in steps of 0.001
Dropout level:
97 to 98% of pickup
Fwd / reverse reach (sec. ): 0.10 to 500.00  in steps of 0.01
Left and right blinders (sec. ): 0.10 to 500.00  in steps of 0.01
Impedance accuracy:
±5%
Fwd / reverse angle impedances: 40 to 90° in steps of 1
Angle accuracy:
±2°
Characteristic limit angles: 40 to 140° in steps of 1
Timers:
0.000 to 65.535 s in steps of 0.001
Timing accuracy:
±3% or 4 ms, whichever is greater
LOAD ENCROACHMENT
Responds to:
Positive-sequence quantities
Minimum voltage:
0.000 to 3.000 pu in steps of 0.001
Reach (sec. ):
0.02 to 250.00  in steps of 0.01
Impedance accuracy:
±5%
Angle:
5 to 50° in steps of 1
Angle accuracy:
±2°
Pickup delay:
0 to 65.535 s in steps of 0.001
Reset delay:
0 to 65.535 s in steps of 0.001
Time accuracy:
±3% or ±4 ms, whichever is greater
Operate time:
< 30 ms at 60 Hz
°
in steps of 1