GE D60 Instruction Manual page 628

Line distance protection system ur series
Hide thumbs Also See for D60:
Table of Contents

Advertisement

B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 40 of 72)
ADDR
REGISTER NAME
78AB
PMU 1 Test df/dt
Phasor Measurement Unit Recording Values (Read Only) (4 modules)
7900
PMU 1 Available Records
7901
PMU 1 Second Per Record
7903
PMU 1 Last Cleared Date
Phasor Measurement Unit Network Reporting Configuration (Read/Write Setting)
7914
PMU Network Reporting Function
7915
PMU Network Reporting ID Code
7916
PMU TCP port number
7917
PMU UDP port number 1
B
7918
PMU UDP port number 2
Phasor Measurement Unit Calibration (Read/Write Setting) (4 modules)
7919
PMU Va Calibration Angle
791A
PMU Va Calibration Magnitude
791B
PMU Vb Calibration Angle
791C
PMU Vb Calibration Magnitude
791D
PMU Vc Calibration Angle
791E
PMU Vc Calibration Magnitude
791F
PMU Vx Calibration Angle
7920
PMU Vx Calibration Magnitude
7921
PMU Ia Calibration Angle
7922
PMU Ia Calibration Magnitude
7923
PMU Ib Calibration Angle
7924
PMU Ib Calibration Magnitude
7925
PMU Ic Calibration Angle
7926
PMU Ic Calibration Magnitude
7927
PMU Ig Calibration Angle
7928
PMU Ig Calibration Magnitude
7929
PMU Sequence Voltage Shift Angle
792A
PMU Sequence Current Shift Angle
Phasor Measurement Unit Triggering (Read/Write Setting) (4 modules)
7970
PMU 1 User Trigger
Phasor Measurement Unit Current Trigger (Read/Write Setting) (4 modules)
7980
PMU 1 Current Trigger Function
7981
PMU 1 Current Trigger Pickup
7982
PMU 1 Current Trigger Pickup Time
7983
PMU 1 Current Trigger Dropout Time
7984
PMU 1 Current Trigger Block (3 items)
798A
PMU 1 Current Trigger Target
798B
PMU 1 Current Trigger Events
Phasor Measurement Unit df/dt Trigger (Read/Write Setting)
79B0
PMU 1 df/dt Trigger Function
79B1
PMU 1 df/dt Trigger Raise
79B2
PMU 1 df/dt Trigger Fall
79B3
PMU 1 df/dt Trigger Pickup Time
79B4
PMU 1 df/dt Trigger Dropout Time
79B5
PMU 1 df/dt Trigger Block (3 items)
79BB
PMU 1 df/dt Trigger Target
79BC
PMU 1 df/dt Trigger Events
Underfrequency (Read/Write Setting) (6 modules)
7A80
Underfreqency Function
7A81
Underfrequency Block
7A83
Min Current
7A84
Underfrequency Pickup
B-48
RANGE
-10 to 10
0 to 65535
0 to 6553.5
0 to 400000000
0 to 1
1 to 65534
1 to 65535
1 to 65535
1 to 65535
-5 to 5
95 to 105
-5 to 5
95 to 105
-5 to 5
95 to 105
-5 to 5
95 to 105
-5 to 5
95 to 105
-5 to 5
95 to 105
-5 to 5
95 to 105
-5 to 5
95 to 105
-180 to 180
-180 to 180
0 to 4294967295
0 to 1
0.1 to 30
0 to 600
0 to 600
0 to 4294967295
0 to 2
0 to 1
0 to 1
0.1 to 15
0.1 to 15
0 to 600
0 to 600
0 to 4294967295
0 to 2
0 to 1
0 to 1
0 to 4294967295
0.1 to 1.25
20 to 65
D60 Line Distance Protection System
APPENDIX B
UNITS
STEP
FORMAT
Hz/s
0.01
F002
---
1
F001
---
0.1
F001
---
1
F050
---
1
F102
---
1
F001
---
1
F001
---
1
F001
---
1
F001
°
0.05
F002
%
0.1
F002
°
0.05
F002
%
0.1
F002
°
0.05
F002
%
0.1
F002
°
0.05
F002
%
0.1
F002
°
0.05
F002
%
0.1
F002
°
0.05
F002
%
0.1
F002
°
0.05
F002
%
0.1
F002
°
0.05
F002
%
0.1
F002
°
30
F002
°
30
F002
---
1
F300
---
1
F102
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F102
Hz/s
0.01
F001
Hz/s
0.01
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F102
---
1
F300
pu
0.01
F001
Hz
0.01
F001
DEFAULT
0
0
0
0
0 (Disabled)
1
4712
4713
4714
0
1000
0
1000
0
1000
0
1000
0
1000
0
1000
0
1000
0
1000
0
0
0
0 (Disabled)
1800
10
100
0
0 (Self-reset)
0 (Disabled)
0 (Disabled)
25
25
10
100
0
0 (Self-reset)
0 (Disabled)
0 (Disabled)
0
10
5950
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents