APPENDIX B
F239
ENUMERATION: REAL TIME CLOCK DAYLIGHT SAVINGS
TIME START DAY INSTANCE
value
instance
0
First
1
Second
2
Third
3
Fourth
4
Last
F243
ENUMERATION: FIELD UNIT TYPE
0 = CC-05, 1 = CV-05, 2 = CC-01, 3 = CV-01
F244
ENUMERATION: PROCESS CARD PORT
0 = H4a, 1 = H4b 2 = H3a, 3 = H3b, 4 = H2a, 5 = H2b, 6 = H1a,
7 = H1b
F245
ENUMERATION: TEST MODE FUNCTION
Value
Function
0
Disabled
1
Isolated
2
Forcible
F257
ENUMERATION: PROCESS CARD DSP CONFIGURATION
value
instance
0
CC
1
CV
2
CD
3
VC
4
VV
5
VD
6
DC
7
DV
8
DD
F260
ENUMERATION: DATA LOGGER MODE
0 = Continuous, 1 = Trigger
GE Multilin
F261
ENUMERATION: BANK REDUNDANCY TYPE
0 = None, 1 = Dependability Biased, 2 = Security Biased
F263
ENUMERATION: PROCESS BUS SYSTEM STATUS
0 = N/A, 1 = OK, 2 = Fail
F270
ENUMERATION: FAULT REPORT VT SUBSTITUTION
Value
0
1
2
F300
UR_UINT16: FLEXLOGIC BASE TYPE (6-bit type)
The FlexLogic BASE type is 6 bits and is combined with a 9 bit
descriptor and 1 bit for protection element to form a 16 bit value.
The combined bits are of the form: PTTTTTTDDDDDDDDD,
where P bit if set, indicates that the FlexLogic type is associated
with a protection element state and T represents bits for the BASE
type, and D represents bits for the descriptor.
The values in square brackets indicate the base type with P prefix
[PTTTTTT] and the values in round brackets indicate the descrip-
tor range.
[0] Off(0) – this is boolean FALSE value
[0] On (1) – this is boolean TRUE value
[2] CONTACT INPUTS (1 to 96)
[3] CONTACT INPUTS OFF (1 to 96)
[4] VIRTUAL INPUTS (1 to 64)
[6] VIRTUAL OUTPUTS (1 to 96)
[10] CONTACT OUTPUTS VOLTAGE DETECTED (1 to 64)
[11] CONTACT OUTPUTS VOLTAGE OFF DETECTED (1 to 64)
[12] CONTACT OUTPUTS CURRENT DETECTED (1 to 64)
[13] CONTACT OUTPUTS CURRENT OFF DETECTED (1 to 64)
[14] REMOTE INPUTS (1 to 32)
[28] INSERT (via keypad only)
[32] END
[34] NOT (1 INPUT)
[36] 2 INPUT XOR (0)
[38] LATCH SET/RESET (2 inputs)
[40] OR (2 to 16 inputs)
[42] AND (2 to 16 inputs)
[44] NOR (2 to 16 inputs)
[46] NAND (2 to 16 inputs)
[48] TIMER (1 to 32)
[50] ASSIGN VIRTUAL OUTPUT (1 to 96)
[52] SELF-TEST ERROR (see F141 for range)
[56] ACTIVE SETTING GROUP (1 to 6)
[62] MISCELLANEOUS EVENTS (see F146 for range)
[64 to 127] ELEMENT STATES
D60 Line Distance Protection System
B.4 MEMORY MAPPING
Description
None
I_0
V_0
B
B-97