GE D60 Instruction Manual page 636

Line distance protection system ur series
Hide thumbs Also See for D60:
Table of Contents

Advertisement

B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 48 of 72)
ADDR
REGISTER NAME
9A20
Teleprotection Output 1-n Operand (16 items)
9A40
Teleprotection Output 2-n Operand (16 items)
Teleprotection Channel Tests (Read Only)
9AA0
Teleprotection Channel 1 Status
9AA1
Teleprotection Channel 1 Number of Lost Packets
9AA2
Teleprotection Channel 2 Status
9AA3
Teleprotection Channel 2 Number of Lost Packets
9AA4
Teleprotection Network Status
9AAF
Teleprotection Channel 1 Input States
9AB0
Teleprotection Channel 2 Input States
B
9AC0
Teleprotection Input 1 States, 1 per register (16 items)
9AD0
Teleprotection Input 2 States, 1 per register (16 items)
VT Fuse Failure (Read/Write Setting) (6 modules)
A09A
VT Fuse Failure Function
A09B
VT Fuse Failure Neutral Wire Open Function
A09C
VT Fuse Failure Neutral Wire Open 3rd Harmonic Pickup
A09D
...Repeated for module number 2
A0A0
...Repeated for module number 3
A0A3
...Repeated for module number 4
A0A6
...Repeated for module number 5
A0A9
...Repeated for module number 6
A0AC
VTFF x V0 3rd harmonic
Selector switch actual values (read only)
A210
Selector switch 1 position
A211
Selector switch 2 position
Selector switch settings (read/write, 2 modules)
A280
Selector 1 Function
A281
Selector 1 Range
A282
Selector 1 Timeout
A283
Selector 1 Step Up
A285
Selector 1 Step Mode
A286
Selector 1 Acknowledge
A288
Selector 1 Bit0
A28A
Selector 1 Bit1
A28C
Selector 1 Bit2
A28E
Selector 1 Bit Mode
A28F
Selector 1 Bit Acknowledge
A291
Selector 1 Power Up Mode
A292
Selector 1 Target
A293
Selector 1 Events
A294
Reserved (10 items)
A29E
...Repeated for Selector 2
Digital Counter (Read/Write Setting) (8 modules)
A300
Digital Counter 1 Function
A301
Digital Counter 1 Name
A307
Digital Counter 1 Units
A30A
Digital Counter 1 Block
A30C
Digital Counter 1 Up
A30E
Digital Counter 1 Down
A311
Digital Counter 1 Preset
A313
Digital Counter 1 Compare
A315
Digital Counter 1 Reset
A317
Digital Counter 1 Freeze/Reset
B-56
RANGE
0 to 4294967295
0 to 4294967295
0 to 2
0 to 65535
0 to 2
0 to 65535
0 to 2
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 3
0 to 999999.999
1 to 7
1 to 7
0 to 1
1 to 7
3 to 60
0 to 4294967295
0 to 1
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 1
0 to 4294967295
0 to 2
0 to 2
0 to 1
---
0 to 1
---
---
0 to 4294967295
0 to 4294967295
0 to 4294967295
–2147483647 to
2147483647
–2147483647 to
2147483647
0 to 4294967295
0 to 4294967295
D60 Line Distance Protection System
APPENDIX B
UNITS
STEP
FORMAT
---
1
F300
---
1
F300
---
1
F134
---
1
F001
---
1
F134
---
1
F001
---
1
F134
---
1
F500
---
1
F500
---
1
F108
---
1
F108
---
1
F102
---
1
F102
pu
0.001
F001
V
0.001
F060
---
1
F001
---
1
F001
---
1
F102
---
1
F001
s
0.1
F001
---
1
F300
---
1
F083
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F083
---
1
F300
---
1
F084
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
---
F205
---
---
F206
---
1
F300
---
1
F300
---
1
F300
---
1
F004
---
1
F004
---
1
F300
---
1
F300
DEFAULT
0
0
1 (OK)
0
1 (OK)
0
2 (n/a)
0
0
0 (Off)
0 (Off)
0 (Disabled)
0 (Disabled)
100
0
0
1
0 (Disabled)
7
50
0
0 (Time-out)
0
0
0
0
0 (Time-out)
0
0 (Restore)
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
"Counter 1"
(none)
0
0
0
0
0
0
0
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents