5 SETTINGS
h) COMPENSATED OVERVOLTAGE (ANSI 59P, IEC PTOV)

PATH: SETTINGS
GROUPED ELEMENTS
 COMPENSATED
 OVERVOLTAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The compensated overvoltage function is intended to provide protection against an overvoltage due to the opening of the
remote terminal of a transmission line – the so called the Ferranti effect. This could be achieved using a transfer-tripping
scheme. However, with high voltage, more corona may exist on the line and inhibit the proper reception of a carrier-trans-
fer-trip signal. Also, the presence of a line with an open terminal in weak systems can raise the voltage level of the local
bus. Detecting and tripping a line with an open terminal can prevent tripping at the local bus in this case.
Figure 5–123: TRANSMISSION LINE WITH REMOTE TERMINAL OPEN
GE Multilin

SETTING GROUP 1(6)
VOLTAGE ELEMENTS
COMPENSATED OV
FUNCTION: Disabled
COMPENSATED OV
SOURCE: SRC 1
COMPENSATED OV Zc
MAG: 2.00 Ω
COMPENSATED OV Zc
ANG: 90°
COMPENSATED OV
I_1max: 0.20 pu
COMPENSATED OV STG1
PICKUP: 1.300 pu
COMPENSATED OV STG1
DELAY: 1.00 s
COMPENSATED OV STG2
PICKUP: 1.300 pu
COMPENSATED OV STG2
DELAY: 1.00 s
COMPENSATED OV STG3
PICKUP: 1.300 pu
COMPENSATED OV STG3
DELAY: 1.00 s
COMPENSATED OV BLK:
Off
COMPENSATED OV
TARGET: Self-reset
COMPENSATED OV
EVENTS: Disabled
D60 Line Distance Protection System
5.6 GROUPED ELEMENTS

COMPENSATED OVERVOLTAGE
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: 0.00 to 500.00 ohms in steps of 0.01
Range: 30 to 90° in steps of 1
Range: 0.01 to 1.00 pu in steps of 0.01
Range: 0.250 to 3.000 pu in steps of 0.01
Range: 0.00 to 600.00 seconds in steps of 0.01
Range: 0.250 to 3.000 pu in steps of 0.01
Range: 0.00 to 600.00 seconds in steps of 0.01
Range: 0.250 to 3.000 pu in steps of 0.01
Range: 0.00 to 600.00 seconds in steps of 0.01
Range: FlexLogic™ operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled