5.6 GROUPED ELEMENTS
e) NEGATIVE SEQUENCE OVERVOLTAGE (ANSI 59Q, IEC PTOV)

PATH: SETTINGS
GROUPED ELEMENTS
 NEG SEQ OV1
There are three negative-sequence overvoltage elements available.
5
The negative-sequence overvoltage element may be used to detect loss of one or two phases of the source, a reversed
phase sequence of voltage, or a non-symmetrical system voltage condition.
SETTING
NEG SEQ OV1
FUNCTION:
Disabled = 0
Enabled = 1
SETTING
NEG SEQ OV1 BLOCK:
Off = 0
SETTING
NEG SEQ OV1 SIGNAL
SOURCE:
Wye VT
Delta VT
V_2
5-220
SETTING GROUP 1(6)
NEG SEQ OV1
FUNCTION: Disabled
NEG SEQ OV1 SIGNAL
MESSAGE
SOURCE: SRC 1
NEG SEQ OV1 PICKUP:
MESSAGE
0.300 pu
NEG SEQ OV1 PICKUP
MESSAGE
DELAY:
NEG SEQ OV1 RESET
MESSAGE
DELAY:
NEG SEQ OV1 BLOCK:
MESSAGE
Off
NEG SEQ OV1 TARGET:
MESSAGE
Self-reset
NEG SEQ OV1 EVENTS:
MESSAGE
Disabled
SETTING
NEG SEQ OV1 PICKUP:
AND
RUN
V_2 or 3 × V_2 PKP
3 × V_2
Figure 5–120: NEGATIVE-SEQUENCE OVERVOLTAGE SCHEME LOGIC
D60 Line Distance Protection System

VOLTAGE ELEMENTS
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: 0.000 to 1.250 pu in steps of 0.001
Range: 0.00 to 600.00 s in steps of 0.01
0.50 s
Range: 0.00 to 600.00 s in steps of 0.01
0.50 s
Range: FlexLogic™ operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
SETTINGS
NEG SEQ OV1 PICKUP
DELAY:
NEG SEQ OV1 RESET
DELAY:
t
PKP
t
RST
5 SETTINGS

NEG SEQ OV1(3)
FLEXLOGIC OPERANDS
NEG SEQ OV1 PKP
NEG SEQ OV1 DPO
NEG SEQ OV1 OP
827839A3.CDR