5.4 SYSTEM SETUP
a) MAIN MENU

PATH: SETTINGS
SYSTEM SETUP
 PHASOR MEASUREMENT
 UNIT
The D60 Line Distance Protection System is provided with an optional phasor measurement unit feature.
This feature is specified as a software option at the time of ordering. The number of phasor measurement
units available is also dependent on this option. Refer to the Ordering section of chapter 2 for additional
details.
UR Synchrophasor Implementation
are used within protection relays. If these phasors are referenced to a common time base they are referred to as
PHASORS
a
. A vastly improved method for tracking power system dynamic phenomena for improved power system
SYNCHROPHASOR
5
monitoring, protection, operation, and control can be realized if Synchrophasors from different locations within the power
system are networked to a central location.
The D60 offers PMU features over two communication standards, IEC61850-9-5 and C37.118. The complete Synchropha-
sor implementation for Firmware version 7.0 is shown in the figure below.
UR Implementation of IEC61850-90-5
Synchrophasor data as measured and calculated by phasor measurement units (PMUs) is very useful to assess the condi-
tion of the electrical power network. The IEEE C37.118-2005 standard defines synchrophasors and related message for-
mats to transmit synchrophasor data. Synchrophasor streaming via IEEE C37.118 has proven to work but the desire to
5-98


PHASOR MEASUREMENT UNIT

 PHASOR MEASUREMENT
 UNIT 1
 AGGREGATOR
MESSAGE
 UNIT 1
 IEC 90-5 MSVCB
MESSAGE
 CONFIGURATION
 REPORTING OVER
MESSAGE
 NETWORK
Figure 5–38: COMPLETE SYNCHROPHASOR IMPLEMENTATION
D60 Line Distance Protection System
5.4.7 PHASOR MEASUREMENT UNIT
See below.
See page 5–115.
See page 5–117.
See page 5-119.
5 SETTINGS