5 SETTINGS
SESSION LOCKOUT: This setting specifies the number of failed authentications (the default is three and the maxi-
mum is 99) before the device blocks subsequent authentication attempts for the lockout period. A value of zero means
lockout is disabled.
SESSION LOCKOUT PERIOD: This setting specifies the period of time in minutes of a lockout period (the default is
three and the maximum is 9999). A value of 0 means that there is no lockout period.
e) RESTORE DEFAULTS
PATH: SETTINGS
PRODUCT SETUP
 RESTORE DEFAULTS
LOAD FACTORY DEFAULTS: This setting is used to reset all the settings, communication and security passwords. An
Administrator role is used to change this setting and a Supervisor role (if not disabled) approves it.
f) SUPERVISORY
PATH: SETTINGS
PRODUCT SETUP
 SUPERVISORY
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
GE Multilin

SECURITY
RESTORE DEFAULTS
LOAD FACTORY
DEFAULTS: No

SECURITY
SUPERVISORY
LOCAL
AUTHENTICATION:Yes
Bypass Access:
Disable
LOCK RELAY:
Disable
FACTORY SERVICE:
MODE: Disable
 SELF TESTS
SUPERVISOR ROLE:
Disable
SERIAL INACTIVITY
TIMEOUT: 3
D60 Line Distance Protection System
5.2 PRODUCT SETUP
Range: Yes, No
Range: Yes, No
Range: Enable, Disable
Range: Enable, Disable
Range: Enable, Disable
See below
Range: Enable, Disable
Range: 1 to 9999 minutes