APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 47 of 72)
ADDR
REGISTER NAME
IEC 61850 Received Integers (Read/Write Setting) (16 modules)
98A0
IEC61850 GOOSE UInteger 1 default value
98A2
IEC61850 GOOSE UInteger input 1 mode
98A3
...Repeated for IEC61850 GOOSE UInteger 2
98A6
...Repeated for IEC61850 GOOSE UInteger 3
98A9
...Repeated for IEC61850 GOOSE UInteger 4
98AC
...Repeated for IEC61850 GOOSE UInteger 5
98AF
...Repeated for IEC61850 GOOSE UInteger 6
98B2
...Repeated for IEC61850 GOOSE UInteger 7
98B5
...Repeated for IEC61850 GOOSE UInteger 8
98B8
...Repeated for IEC61850 GOOSE UInteger 9
98BB
...Repeated for IEC61850 GOOSE UInteger 10
98BE
...Repeated for IEC61850 GOOSE UInteger 11
98C1
...Repeated for IEC61850 GOOSE UInteger 12
98C4
...Repeated for IEC61850 GOOSE UInteger 13
98C7
...Repeated for IEC61850 GOOSE UInteger 14
98CA
...Repeated for IEC61850 GOOSE UInteger 15
98CD
...Repeated for IEC61850 GOOSE UInteger 16
FlexElement Actuals (Read Only) (16 modules)
9000
FlexElement 1 Actual
9902
FlexElement 2 Actual
9904
FlexElement 3 Actual
9906
FlexElement 4 Actual
9908
FlexElement 5 Actual
990A
FlexElement 6 Actual
990C
FlexElement 7 Actual
990E
FlexElement 8 Actual
Breaker Restrike (Read/Write Setting) (3 modules)
9930
Breaker restrike 1 function
9931
Breaker restrike 1 block
9933
Breaker restrike 1 signal source
9934
Breaker restrike 1 pickup
9935
Breaker restrike 1 reset delay
9936
Breaker restrike 1 HF detect
9937
Breaker restrike 1 breaker open
9939
Breaker restrike 1 open command
993B
Breaker restrike 1 close command
993D
Breaker restrike 1 target
993E
Breaker restrike 1 events
993F
Reserved (2 items)
9941
...Repeated for breaker restrike 2
Teleprotection Inputs/Outputs Commands (Read/Write Command)
9980
Teleprotection Clear Lost Packets
Teleprotection Inputs/Outputs (Read/Write Settings)
9990
Teleprotection Function
9991
Teleprotection Number of Terminals
9992
Teleprotection Number of Channels
9993
Teleprotection Local Relay ID
9994
Teleprotection Terminal 1 ID
9995
Teleprotection Terminal 2 ID
9996
Reserved (10 items)
9A00
Teleprotection Input 1-n Default States (16 items)
9A10
Teleprotection Input 2-n Default States (16 items)
GE Multilin
RANGE
0 to 429496295
0 to 1
-2147483.647 to 2147483.647
-2147483.647 to 2147483.647
-2147483.647 to 2147483.647
-2147483.647 to 2147483.647
-2147483.647 to 2147483.647
-2147483.647 to 2147483.647
-2147483.647 to 2147483.647
-2147483.647 to 2147483.647
0 to 1
0 to 4294967295
0 to 5
0.10 to 2.00
0 to 65.535
0 to 1
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 2
0 to 1
0 to 1
0 to 1
0 to 1
2 to 3
1 to 2
0 to 255
0 to 255
0 to 255
0 to 1
0 to 3
0 to 3
D60 Line Distance Protection System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F003
---
1
F491
---
0.001
F004
---
0.001
F004
---
0.001
F004
---
0.001
F004
---
0.001
F004
---
0.001
F004
---
0.001
F004
---
0.001
F004
---
1
F102
---
1
F300
---
1
F167
pu
0.01
F001
s
0.001
F001
---
1
F102
---
1
F300
---
1
F300
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F126
---
1
F102
---
1
F001
---
1
F001
---
1
F001
---
1
F001
---
1
F001
---
---
F001
---
1
F086
---
1
F086
DEFAULT
1000
0 (Default
Value)
B
0
0
0
0
0
0
0
0
0 (Disabled)
0
0 (SRC 1)
500
100
1 (Enabled)
0
0
0
0 (Self-reset)
0 (Disabled)
0
0 (No)
0 (Disabled)
2
1
0
0
0
0
0 (Off)
0 (Off)