Appendix C: IP Downloading

General Information

The 7847i/7847i-E can be used to provide high-speed up/downloading to Honeywell VISTA
and LynxR-I control panels. This allows site maintenance independent of central station
monitoring, and modification to sites through an Intranet or globally via the Internet.
Residential panels that support IP downloading (e.g., Vista-20P and LynxR-I) are connected
to the unit through the ECP bus. Currently, commercial controls such as VISTA-128BP and
FBP support IP downloading through use of a Direct Wire connection (using the trigger
cable).
U L

Direct Wire Setup

To perform IP up/downloading using Direct Wire, the unit requires that Direct Wire
downloading over IP programming is enabled (Direct Wire Y/N), and that the ECP Device
Address on which the unit communicates with the control panel as a keypad is entered
(Keypad Address). Additionally, the 7847i/7847i-E must be connected by cable as shown
below to the panels listed.
NOTES:
1. For Direct Wire IP downloading on Commercial Fire panels (e.g. VISTA-128FBP,
FA1700C), Program Field 3*19 Enable J2 Header Printer Port must be set to "1".
2. This feature is not available if device is set for zone trigger mode.
1
PARTS SUPPLIED WITH DOWNLOADER KIT P/N VBPCOMKIT
1
2
PARTS SUPPLIED WITH DOWNLOADER KIT P/N VFBPCOMKIT
Downloading may only be performed if a technician is at the site.
VISTA-128BP/250BP
FA1660C
J8 CONNECTOR
2
3
4
5
6
7
8
9
NU
4142 TR CABLE
VISTA-128FBP/250FBP
FA1670C /FA1700C
J2 CONNECTOR
3
4
5
6
7
8
9
TO
AUX PWR 1
OUTPUT
4142 TR CABLE
Figure 16. Cable Connections for IP Downloading
PROGRAMMER
PORT
WHITE
BLUE
K4668WH
RJ 11 CABLE
PROGRAMMER
PORT
4100SM
+ (TO TERM 11)
+ PWR
8
- (TO TERM 12)
7
- (GND)
RXD
6
not used
5
not used
4
3
TXD
not used
2
not used
1
RED
BLUE WHITE
7847i / 7847i-E
TB 1
1
2
3
4
5
6
7
8
9
10
11
7847i-E-026-V0
7847i / 7847i-E
TB 1
1
2
3
4
5
6
7
8
9
10
11
K14394LF 25-PIN TO RJ11 CABLE
7847i-E-027-V0
C-1