7800 SERIES
S7830
Expanded Annunciator

APPLICATION

The S7830 Expanded Annunciator is an enhancement module
for use with 7800 SERIES Relay Modules. The S7830 is a
microprocessor-based device designed to monitor the status
of a series string of limit, control, and interlock contacts for a
commercial or industrial burner. The S7830 acts as a system
monitor and enhances fault and status messages of the 7800
SERIES burner control.

FEATURES

• 26 status light emitting diodes (LED).
• Front panel LED array, arranged in a pattern to clearly
indicate the flow of line voltage through the string of
limits, controls and interlocks.
• Selectable current and first-out LED array display
status.
• Power and proper operation indicating LED.
• Common Universal Mounting Subbase (Q7800A or B).
• 21 monitored contact points.
• Access for external electrical voltage checks.
• Communication interface capability.
• Capable of programmable limit or interlock messages
using the S7800A1142 Keyboard Display Module
(KDM).
• Open Lockout interlocks are indicated with a flashing
status LED when used with Relay Module Models with
Lockout Interlock feature.
• Hold messages displayed on the KDM are enhanced
with the Expanded Annuciator terminal description
information that is causing the hold (low water cutoff
for example).
• LED operational test.
• 36 additional 7800 SERIES fault and hold messages.
Application ........................................................................
Features ...........................................................................
Specifications ...................................................................
Ordering Information .........................................................
Principal Technical Features ............................................
Installation ........................................................................
Wiring ...............................................................................
Operation .........................................................................
PRODUCT DATA
Contents
1
1
2
2
4
4
5
9
65-0101-03

Advertisement

loading

Summary of Contents for Honeywell 7800 SERIES

  • Page 1: Table Of Contents

    The S7830 Expanded Annunciator is an enhancement module with the Expanded Annuciator terminal description for use with 7800 SERIES Relay Modules. The S7830 is a information that is causing the hold (low water cutoff microprocessor-based device designed to monitor the status for example).
  • Page 2: Specifications

    If you have additional questions, need further information, or would like to comment on our products or services, please write or phone: 1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory). 2. Honeywell Customer Care...
  • Page 3 7800 SERIES S7830 EXPANDED ANNUNCIATOR Environmental Ratings:\ Canadian Standards Association certified: LR95329. Ambient Temperature Range: Factory Mutual Approved. Operating: -40°F to +140°F (-40°C to +60°C). IRI Acceptable. Storage: -40°F to +150°F (-40°C to +66°C). Federal Communications Commission: Part 15, Class B Humidity: 85% continuous, noncondensing.
  • Page 4: Principal Technical Features

    PRINCIPAL TECHNICAL FEATURES INSTALLATION The S7830 Expanded Annunciator is an enhancement module for use with 7800 SERIES Relay Modules. The S7830 is a microprocessor-based device designed to monitor the status of a series string of limit, control and interlock contacts WARNING for a commercial or industrial burner.
  • Page 5: Wiring

    RS-485 ControlBus commercial environment. Operation of this to the 7800 SERIES Relay Module. The S7830 must be equipment in a residential area may cause within 1000 feet (305 meters) of the 7800 SERIES interference;...
  • Page 6 120V, 50/60Hz POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. IN DUAL FUEL SYSTEMS, 7800 SERIES-T6 CAN BE CONNECTED TO ANY POINT FROM 6 TO 11, INCLUSIVE. (ANYTHING BEFORE THIS POINT IN CONSIDERED A LIMIT AND ANYTHING AFTER IT IS CONSIDERED AN INTERLOCK DEVICE SPECIFIC.)
  • Page 7 120V, 50/60HZ POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 7800 SERIES TERMINAL 17 CAN BE CONNECTED TO ANY POINT S7830 TERMINAL 17 THROUGH 11 OR 17 THROUGH 19. (ANYTHING BEFORE CONNECTION ARE RUNNING LIMITS AND ANYTHING AFTER IT IS CONSIDERED LOCKOUT INTERLOCKS DEVICE SPECIFIC.)
  • Page 8 120V, 50/60Hz POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 7800 SERIES TERMINAL 6 CAN BE CONNECTED TO ANY POINT S7830 TERMINAL 6 THROUGH 19. (ANYTHING BEFORE CONNECTION ARE RUNNING LIMITS AND ANYTHING AFTER IT IS CONSIDERED LOCKOUT INTERLOCKS DEVICE SPECIFIC.) PLACE JUMPERS ON S7830 WIRING SUBBASE ONLY FOR UNUSED CONTROL, LIMIT, OR INTERLOCKS.
  • Page 9: Operation

    7800 SERIES S7830 EXPANDED ANNUNCIATOR S7830 RS485 CONTROLBUS CONNECTOR 120 OHM RESISTOR 7800 SERIES RELAY MODULE S7800 CONNECTION THREE WIRE SHIELDED CABLE AND 120 OHM (1/4 WATT) TERMINATING RESISTOR MAY BE REQUIRED. CABLE SHIELD MUST BE TERMINATED TO GROUND AT BOTH ENDS. IF Fig.
  • Page 10 7800 SERIES S7830 EXPANDED ANNUNCIATOR NOTE: Not all 7800 SERIES devices lock out for an open twice each second. For example, if the Standby hold is being interlock. Annunciation is available as hold caused by the Burner Switch being open, the Standby hold messages but an alarm will not be generated.
  • Page 11 Reset Keypad after a system (2) LED OFF indicates the LED array is in a Current lockout. Once the 7800 SERIES Relay Module is reset, the Status mode, power is off, or the LED is S7830 LED array automatically will be reset to the Current defective.
  • Page 12 7800 SERIES S7830 EXPANDED ANNUNCIATOR Table 2. Expanded Annunciator Informational Index. Selectable Message Display Value Description LowGasPres 1 or 0 The low gas pressure limit switch is open (0) or closed (1). Airflow Sw The airflow interlock switch is open (0) or closed (1).
  • Page 13 7800 SERIES S7830 EXPANDED ANNUNCIATOR Table 4. Expanded Annunciator Lockout Codes. Message Description LOCKOUT nna Auxiliary Limit # 1 was open. *Aux.Limit#1* LOCKOUT nnb Auxiliary Limit # 2 was open. *Aux.Limit#2* LOCKOUT nnc Low water cutoff was open. *LWCO* LOCKOUT nnd Appliance high limit was exceeded.
  • Page 14 7800 SERIES S7830 EXPANDED ANNUNCIATOR Table 5. Expanded Annunciator Current Status Messages (Continued) Message Description FuelSelectOff Fuel Select switch is off. BothFuelSelect Both fuel select inputs are on. High Oil Pres. High Oil Pressure Low Oil Pres. Low Oil Pressure Low Oil Temp.
  • Page 15 7800 SERIES S7830 EXPANDED ANNUNCIATOR 65-0101—03...
  • Page 16 7800 SERIES S7830 EXPANDED ANNUNCIATOR Automation and Control Solutions Honeywell International Inc. Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, MN 55422 Toronto, Ontario M1V 4Z9 customer.honeywell.com ® U.S. Registered Trademark © 2008 Honeywell International Inc.

This manual is also suitable for:

S7830