Honeywell AlarmNet 7847i-E Installation And Setup Manual page 29

Internet/intranet communication modules with remote services
Hide thumbs Also See for AlarmNet 7847i-E:
Table of Contents

Advertisement

PROMPTS
IP Flt Time
29
(60 mins)_
Flt Rel ON Y/N
30
(N)_
Tamper Rpt Y/N
31
(Y)_
Lynx Panic Y/N
32
(N)_
If desired, 4204 mode supports two optional hardwire zone input triggers by making connections to the module's zone
6 and/or zone 7 terminals and programming the appropriate zone trigger options below.
NOTE: These triggers are not available when using 2-4204 mode.
Zone Trigger Mode provides six hardwire zone input triggers by making connections to the module's zone terminals
and programming the appropriate zone trigger options below. Zones are numbered 1-7, with zone 2 serving as a
reporting zone only (see Bell Output Zone below).
Bell Output Zone 1 (and 2): The zone 1 and 2 terminal can detect both pulsed and steady signals. If connecting the
7847i-E
bell output to the 7847i/
7847i/7847i-E reports an alarm on zone 1 (fire) when it detects a pulsed signal and an alarm on zone 2 (burglary) when
it detects a steady signal.
Telco Zone and Open/Close Zone: Dedicated zones can be assigned as the telco fault zone and/or an open/close
(arm/disarm) reporting zone. When triggered, these zones report a telco line fault or open/close report respectively, in
ADEMCO High-Speed format. Connect the appropriate trigger from the control to the selected zone input for each of
these options.
Input Trigger Types: Triggering of each zone input can be programmed to cause an alarm under one of the following
conditions:
• (V+), where a positive voltage causes an alarm for normally low connections (voltage trigger, NO, NC)
• (V–), where a ground trigger causes an alarm for normally high connections (open collector, NO, NC)
• (EOLR) End of Line Resistor, where the input is supervised by a 2K EOL resistor. The zone can be triggered by
4204/
ZONE
ENTRY
2-4204
TRIG.
[00-99]
[Y], [N]
[Y], [N]
[Y], [N]
Important Information Regarding Zone Input Options
zone causes a bell fault on the control panel, enable the "Trip Inputs 1or2" option. The
Section 3: Programming the 7847i/7847i-E
OPTIONS
Enter the time delay (01-99) in minutes before the
7847i/7847i-E notifies the control panel that there
is loss of contact with the network, or enter 00 if
you do not want the unit to alert the control panel
of loss of contact with the network. The unit will
alert the control panel of the loss of contact via a
dedicated status message.
NOTE: Cannot be less than two (02) minutes if
Private LAN is enabled on the 7847i-E and the
Supervision interval is greater than 90 seconds.
UL NOTE: Must be one (01) minute.
If enabled, the fault open collector output is
normally energized to ground, and de-energizes
(open circuit) in the event of a module fault.
Set to [Y] if fail-safe mode is desired.
NOTE: If used, the fault relay will trip when the
following conditions occur: tamper*, loss of
network connectivity*, message communication
failure, the device is not registered and the device
is remotely disabled by AlarmNet.
* Alarm reporting for the noted condition must be
enabled for it to trigger the fault relay.
UL NOTE: Must be set to "Y."
Sends a tamper report on zone 8 when the module
detects a tamper condition. A tamper restore is
automatically sent when the tamper condition
clears.
Applies only if used with a Lynx, LynxR or
LynxR-EN control LRR trigger connected to the
module's zone terminal.
Reports a Panic alarm on zone 3 when the module
detects a single pulse on zone 1.
No restores are generated for a Panic alarm.
DESCRIPTION
3-15

Advertisement

Table of Contents
loading

This manual is also suitable for:

Alarmnet 7847i

Table of Contents