Honeywell AlarmNet 7847i-E Installation And Setup Manual page 21

Internet/intranet communication modules with remote services
Hide thumbs Also See for AlarmNet 7847i-E:
Table of Contents

Advertisement

PROMPTS
IP Flt Time
34
(60 mins)_
Flt Rel ON Y/N
35
(N)_
Tamper Rpt Y/N
36
(Y)_
ECP mode supports two optional hardwire zone input triggers by making connections to the module's zone 6 and/or
zone 7 terminals and programming the appropriate zone trigger options below.
Each zone input can be programmed to cause an alarm under one of the following conditions:
• (V+), where a positive voltage causes an alarm for normally low connections (voltage trigger, NO, NC)
• (V–), where a ground trigger causes an alarm for normally high connections (open collector, NO, NC)
• (EOLR) End of Line Resistor, where the input is supervised by a 2K EOL resistor. The zone can be triggered
by open collector, voltage trigger, NO, NC.
In addition to the above, zones can be programmed for an Inverted Trigger, where the alarm and normal states of
the zones are inverted; this can serve a fail-safe supervisory purpose for certain installations.
These zone inputs can also be programmed for restore reporting, and for delayed reporting, which allows time for
the user to abort false alarms.
NOTE: Optional hardwire zones report in ADEMCO High-Speed format.
Enable Zn6 Y/N
37
(N)_
Zn6 Trigger Type
38
(V+)_
Invert Zn6 Y/N
39
(N)_
Restore Zn6 Y/N
40
(Y)_
Delay Zn6 (secs)
41
(00)_
ENTRY
OPTIONS
[00-99]
[Y], [N]
[Y], [N]
Important Information Regarding Zone Input Options
[Y], [N]
• (V+)
• (V–)
• (EOLR)
[Y], [N]
[Y], [N]
[01-15]
[00] = no delay
Section 3: Programming the 7847i/7847i-E
DESCRIPTION
Enter the time delay (01-99) in minutes before the
7847i/7847i-E notifies the control panel that there is
loss of contact with the network, or enter 00 if you do
not want the unit to alert the control panel of loss of
contact with the network. The 7847i/7847i-E will alert
the control panel of the loss of contact via a dedicated
status message.
NOTE: Cannot be less than two (02) minutes if Private
LAN is enabled on the 7847i-E and the Supervision
interval is greater than 90 seconds.
UL NOTE: Must be one (01) minute.
If enabled, the fault open collector output is normally
energized to ground, and de-energizes (open circuit) in
the event of a module fault.
Set to [Y] if fail-safe mode is desired.
NOTE: If used, the fault relay will trip when the
following conditions occur: tamper*, loss of network
connectivity*, message communication failure, the
device is not registered and the device is remotely
disabled by AlarmNet.
* Alarm reporting for the noted condition must be
enabled for it to trigger the fault relay.
UL NOTE: Must be set to "Y."
Sends a tamper report on zone 6 when the module
detects a tamper condition. A tamper restore is
automatically sent when the tamper condition clears.
Enables alarm reporting for zone 6.
If [N], skip to Prompt 42: "Enable Zn7."
Selects the triggering method for this zone input.
Press the [space] key to scroll through choices.
Inverts the alarm and normal states of the zone 6
trigger; otherwise uses normal input signal.
Enables restore reporting for zone 6.
Defines the reporting delay in seconds for zone 6.