Discharge Pressure Check - Daikin F-Series Service Manual

Inverter multi for 2 rooms
Hide thumbs Also See for F-Series:
Table of Contents

Advertisement

Check
5.1.7

Discharge Pressure Check

Check No.08
Discharge pressure check
5.1.8 Outdoor Unit Fan System Check (With DC Motor)
Check No.09
5.1.9 Power Supply Waveforms Check
Check No.10
Measure the power supply waveform between pins 1 and 2 on the terminal board, and check
the waveform disturbance.
[Fig.1]
250
High
YES
Is the stop valve open?
YES
Is the connection pipe
deformed?
YES
Are the heat exchanger
and air filter dirty?
Not dirty
Check the outdoor unit fan system.
Outdoor unit fan running?
YES
Outdoor unit fan
system
functioning.
Check to see if the power supply waveform is a sine wave (Fig.1).
Check to see if there is waveform disturbance near the zero cross (sections circled in Fig.2)
NO
NO
NO
Dirty
Fan motor
NO
lead wire connector
disconnected?
NO
Go to Check No. 15.
[Fig.2]
SiBE12-712C
Replace the compressor.
Open the stop valve.
Replace the pipe installed at
the site.
Clean.
Replace the compressor.
(R7158)
YES
Reconnect.
(R7159)
Service Diagnosis

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents