Outdoor Unit
Step
2
Cut off the clamp.
Open the putty and
3
remove the each
thermistor.
[S91] : Gas pipe
thermistor
Room A (Black)
Room B (Gray)
[S92] : Liquid pipe
thermistor
Room A (Black)
Room B (Gray)
The figure shows the
4
arrangement of the
assembly of the liquid /
gas thermistor.
274
Procedure
(R7634)
Thermistor (Liquid)
Room A
Thermistor (Gas)
Room A
Thermistor (Liquid)
Room B
Thermistor (Gas)
Room B
(R7635)
Meet the edge of the
thermistor and the clip.
(R7636)
SiBE12-712C
Points
Removal Procedure