Daikin F-Series Service Manual page 287

Inverter multi for 2 rooms
Hide thumbs Also See for F-Series:
Table of Contents

Advertisement

Outdoor Unit
Step
5
There is a nut fixing the
compressor.
Remove the nut with an
open-end spanner.
Before working, make
sure that the refrigerant is
empty in the circuit.
Be sure to apply nitrogen
replacement when
heating up the brazed
part.
Heat up the brazed part
6
of the discharge side
and disconnect.
Heat up the brazed part
7
of the suction side and
disconnect.
8
Lift the compressor up
to remove.
276
Procedure
Points
Warning
Since it may happen that
refrigeration oil in the
compressor will catch fire,
prepare wet cloth so as to
extinguish fire immediately.
Warning
Ventilate when refrigerant
leaks during the work.
(If refrigerant contacts fire, it
will cause to arise toxic gas.)
Warning
Be careful about the four way
valve, pipes and so on, which
were heated up by a gas
(R7641)
brazing machine, so as not to
get burnt your hands.
Caution
From the viewpoint of global
environment protection, do
not discharge the refrigerant
gas in the atmosphere. Make
sure to recover the refrigerant
gas with the recovery system.
(R7642)
(R7643)
SiBE12-712C
Removal Procedure