Mount Racks; Table 8 - Mount Racks - Honeywell HC900 User And Installation Manual

Process and safety controller
Hide thumbs Also See for HC900:
Table of Contents

Advertisement

Mount Racks

Rack assembly information is given in Table 8.
Step
Mount the Rack in the
1
enclosure as follows.
Using the diagrams
below as a guide, mark
the locations for rack
mounting in the
enclosure for the top
holes in the rack.
(See CAUTION and
Note at right.)
Drill and tap for # 10 (or
M4) screws.
Start the mounting
screws (supplied by the
user) in the drilled
holes.
Hang the Rack on the
screws at the top.
Mark the locations for
the bottom screws.
(See CAUTION at
right.)
Drill and tap for # 10 (or
M4) screws.
Remove the rack from
the enclosure.
68
Table 8 – Mount Racks
Procedure
For dimensions of the pattern for drilling holes, refer to the
diagram below.
flakes from falling into the rack, or onto any surface within
the electrical cabinet.
Note: Always mount racks as shown above. That is, never
mount vertically, or with backplane horizontal.
HC900 Process & Safety Controller User and Installation Manual
Comments/References
When drilling holes, prevent metal
Revision 6
21 April 2017

Advertisement

Table of Contents
loading