16 Point Analog Input
Step
4
Connect field wiring. Refer to the appropriate figure for your type of analog input.
RTP A for
inputs 1 to 10
RTP B for
inputs 9 to 16
Notice that Inputs 9 and 10 are connected across RTP A and RTP B.
Not shown: recommended external current loop fuses.
Additionally, on RTP A connect the following terminals: 3-22, 4-23, 7-24, 8-25, 15-26, 16-27, 19-29, 20-30
On RTP B connect the following terminals: 1-22, 2-23, 5-24, 6-25, 13-26, 14-27, 17-28, 18-29
Revision 6
21 April 2017
1
1
2
2
3
3
4
4
5
5
21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
1
2
3
4
5
6
21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
Figure 104 - Voltage input connections
Figure 105 - Current connections with 2-wire transmitter
HC900 Process & Safety Controller User and Installation Manual
Action
6
6
7
7
8
8
9 10 11 12 13 14 15 16 17 18 19 20
9 10 11 12 13 14 15 16 17 18 19 20
7
8
9 10 11 12 13 14 15 16 17 18 19 20
247