Honeywell HC900 User And Installation Manual page 195

Process and safety controller
Hide thumbs Also See for HC900:
Table of Contents

Advertisement

Number
Possible Causes
of Red
Strobes
8 or 9
If 8 flashes, the S1
serial port is reporting a
diagnostic.
If 9 flashes, the S2
serial port is reporting a
diagnostic.
Possible causes are:
 If the port is
configured as a
Modbus or ELN
slave, the data link
layer is reporting
that at least 75% of
the last characters
received have had
a failure reported by
the UART or at
least 75% of the
last messages
received have
been invalid.
 If the port is
configured as a
Modbus Master, at
least 75% of the
last requests to a
particular slave
resulted in no
response or a reply
that failed the data
link protocol.
2
The UART failed its
power-up tests
10
Ethernet port tests
failed during power-up.
Revision 6
21 April 2017
Lead and/or Reserve Controller
Action(s)
1. ASYS and FSYS blocks' HW
OK pins are turned off.
2. If configured as a Modbus
master:
 ASYS and FSYS blocks'
Modbus Master Fail pins are
turned on.
 Slave and read blocks
associated with the slaves
experiencing the failure have
their read pins frozen to the last
value read.
 Slave blocks associated with
the slaves experiencing the
failure have their BAD COMM
and NO SCAN pins turned on.
 IN SCAN STATUS is set to
NO for all slaves experiencing
the failure.
 COMM STATUS is set to BAD
for all slaves experiencing the
failure.
 The slaves with the data link
errors have a non-zero data
link error count.
 The slaves experiencing the
failure are moved to the
background scan rate.
See above
1. E1 or E2 port diagnostic is set to
FAILED.
2. ASYS block's HW OK pin is
turned off.
HC900 Process & Safety Controller User and Installation Manual
User Action
1. Check baud rate
2. Check connectors
3. Check cable polarity
4. Isolate cabling from electrical
interference
5. If RS-232 to RS-485 converter is
used, check its power, switch/jumper
settings, and polarity.
6. If configured as a Modbus master,
use the slave status screens to
determine which slaves are
experiencing the problem. For those
slaves check:
Power
Connections
address
baud rate
parity
number of stop bits
for electrical interference
grounding
termination resistor (if at end
of link)
9. The diagnostic is cleared by
clearing the port's statistics.
Replace CPU module
Replace CPU module.
Honeywell OI
HCDesigner/HC
Indication
Utilities Indication
If the lead's status
If the lead's status
LED is indicating
LED is indicating
the failure, see
the failure, see
NETWORK
Lead Port E1:
PORT E1 or
Network Port
NETWORK
Diagnostics or
PORT E2 in the
Lead Port E2:
"Lead CPU
Network Port
Diagnostics"
Diagnostics in
the "Lead
display.
Diagnostics
If the reserve's
Overview" dialog
status LED is
box.
indicating the
If the reserve's
failure, see
NETWORK
status LED is
PORT E1 or
indicating the
NETWORK
failure, Lead Port
PORT E2 in the
E1: Network Port
"Reserve CPU
Diagnostics or
Diagnostics"
Lead Port E2:
Network Port
display.
Diagnostics in
the "Reserve
Diagnostics
Overview" dialog
box.
181

Advertisement

Table of Contents
loading

Table of Contents