8 Point Analog Output
Step
1
ATTENTION: RTP and cables are intended for permanent installation within their own enclosure.
Mount RTP cable assembly to HC900 Controller (Figure 96).
Remove appropriate key tabs from terminal board to allow mating with the module. See page 85.
Connect terminal block end of desired cable assembly to 8 point Analog Output module at controller.
Choose from:
900RTC-B810
900RTC-B825
900RTC-B850
Install 8 point Analog Output label into the module connector cover.
Connect shield drain wire to the grounding bars at the base of the HC900 rack. All field-wiring
shields must be grounded as described in the shield grounding section (page 81).
2
Mount RTP to DIN rail.
Latch to rail. See page 253.
Connect cable to RTP.
3
Set/verify jumper positions on each RTP as shown.
Module Removal / Insertion Under Power (RIUP) is supported by turning off Switch SW1 to allow removal of
the module from the rack without causing an arc. See page 83.
ATTENTION: SW1 opens the + side of the External 24V Power so that RIUP of module is possible.
See page 243 for RTP internal schematic.
Revision 6
21 April 2017
Remote Terminal Cable assembly, 1.0 meters long
Remote Terminal Cable assembly, 2.5 meters long
Remote Terminal Cable assembly, 5.0 meters long
HC900 Process & Safety Controller User and Installation Manual
Action
Jumper open
Jumper closed
241